2014-11-28 05:39:281) PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE PER
 THE WPB AMEND. TO 2010 FBC SEC.107.2.1.4.
 2) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL OF RECORD PER THE F.A.C. RULE
 61G15-23.001 & 61G15-23.002.
 3) SUBMIT PLANS FOR A "D" OCCUPANCY ( DAYCARE) PER THE
 2010 FBC SEC. 313.1.
 4) THE SUBMITTED PLANS REFERENCE THE 2001 FBC. THE 2010
 EDITION OF THE FBC IS THE CODE IN EFFECT. ALL PLANS
 SHALL BE DESIGNED IN ACCORDANCE WITH THE 2010 FBC.
 5) THE PLANS SHALL INDICATE THE DAYCARE
 SUBCLASSIFICATION IN ACCORDANCE WITH THE 2010 FBC
 SEC.313.2.
 6) DAYCARE OCCUPANCIES SHALL COMPLY WITH 2010 FBC SEC.
 436.
 7) THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
 SHALL COMPLY WITH 2010 FPC TABLE 403.1.
 8) A CHANGE OF OCCUPANCY SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF CHAPTER 9 OF THE 2010 FLORIDA EXISTING
 BUILDING CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  