2014-11-25 10:01:10 | 11/25/2014 |
| PROJECT: APT REMODEL |
| PERMIT#: 14110392 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: PASSED WITH EXCEPTION |
| |
| 1) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 2) ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 |
| FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 |
| FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 |
| |
| 3) RECEPTACLE OUTLETS AT KITCHEN COUNTERTOPS SHALL BE |
| INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| THAN 24" MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| IN THAT SPACE. NEC 210.52(C)(1) |
| |
| 4) PROVIDE LIGHTING OUTLETS WHERE SPECIFIED IN |
| 210.70(A), (B), AND (C)(3) STORAGE OR EQUIPMENT SPACES |
| |
| 5) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| 314 AND 315. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |