2014-11-12 08:54:12 | BUILDING PLAN REVIEW |
| PERMIT: 14110387 |
| ADD: 3200 N. MILITARY TRAIL |
| CONT: ADVANCED ROOFING, INC. |
| TEL: (954)522-6868 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. NOV. 12/ 2014 |
| ACTION: DENIED |
| |
| 1) CHARITY WORK, VALUE SHOWN $6,000.00 DOLLORS VALUE OF |
| WORK. CALCULATED VALUE OF $11,005.00. 108.3* BUILDING |
| PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) ROOFING ENGINEERING FROM ATLANTIC & CARIBBEAN ROOF |
| CONSULTING, DATA SHEET INDICATES NOA # 12-0828.03 PAGE |
| 7. PAGE 8 SUBMITTED MAXIMUM DESIGN PRESSURE OF SHEET #8 |
| IS -75 PSF WITH GENERAL LIMITATION #9. NO ENHANCED |
| FASTENING ALLOWED. SUBMIT THE CORRECT SHEET # 7. |
| |
| 3A) NOA 13-0828.03 SHEET # 7 MAXIMUM DESIGN PRESSURE OF |
| -105 PSF. THE PRODUCT APPROVAL PAGE #7 BASE INSULATION |
| LAYER TYPE OF INSULATION AND INSULATION FASTENER (TABLE |
| 3) IS NOT CIRCLED (IDENTIFIED). THE ENGINEERING LETTER |
| STATES REFER TO RAS 117 FOR INSULATION ATTACHMENTS, |
| PLEASE PROVIDE THE TYPE OF INSULATION TO BE INSTALLED |
| FROM THE LIST IN THE PRODUCT APPROVAL PAGE # 7 AND THE |
| TYPE OF FASTENER PER TABLE 3 AND THE DENSITY OF |
| REQUIRED FASTENERS FOR ZONES 1, 2 & 3. |
| |
| 3B) IF THE PAGE 8 OF THE LISTED ABOVE NOA IS CORRECT |
| THEN THE ENGINEERING LETTER IS WRONG AND WILL REQUIRE A |
| NEW ENGINEERING LETTER. NOTE SHEET # 8 THE MAXIMUM |
| DESIGN PRESSURE OF -75 PSF GENERAL LIMITATION #9. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |