Plan Review Notes
Plan Review Notes For Permit 14110387
Permit Number 14110387
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-12 08:54:12BUILDING PLAN REVIEW
 PERMIT: 14110387
 ADD: 3200 N. MILITARY TRAIL
 CONT: ADVANCED ROOFING, INC.
 TEL: (954)522-6868
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 12/ 2014
 ACTION: DENIED
  
 1) CHARITY WORK, VALUE SHOWN $6,000.00 DOLLORS VALUE OF
 WORK. CALCULATED VALUE OF $11,005.00. 108.3* BUILDING
 PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) ROOFING ENGINEERING FROM ATLANTIC & CARIBBEAN ROOF
 CONSULTING, DATA SHEET INDICATES NOA # 12-0828.03 PAGE
 7. PAGE 8 SUBMITTED MAXIMUM DESIGN PRESSURE OF SHEET #8
 IS -75 PSF WITH GENERAL LIMITATION #9. NO ENHANCED
 FASTENING ALLOWED. SUBMIT THE CORRECT SHEET # 7.
  
 3A) NOA 13-0828.03 SHEET # 7 MAXIMUM DESIGN PRESSURE OF
 -105 PSF. THE PRODUCT APPROVAL PAGE #7 BASE INSULATION
 LAYER TYPE OF INSULATION AND INSULATION FASTENER (TABLE
 3) IS NOT CIRCLED (IDENTIFIED). THE ENGINEERING LETTER
 STATES REFER TO RAS 117 FOR INSULATION ATTACHMENTS,
 PLEASE PROVIDE THE TYPE OF INSULATION TO BE INSTALLED
 FROM THE LIST IN THE PRODUCT APPROVAL PAGE # 7 AND THE
 TYPE OF FASTENER PER TABLE 3 AND THE DENSITY OF
 REQUIRED FASTENERS FOR ZONES 1, 2 & 3.
  
 3B) IF THE PAGE 8 OF THE LISTED ABOVE NOA IS CORRECT
 THEN THE ENGINEERING LETTER IS WRONG AND WILL REQUIRE A
 NEW ENGINEERING LETTER. NOTE SHEET # 8 THE MAXIMUM
 DESIGN PRESSURE OF -75 PSF GENERAL LIMITATION #9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  