Plan Review Notes
Plan Review Notes For Permit 14110334
Permit Number 14110334
Review Stop Z
Sequence Number 1
Notes
Date Text
2014-12-03 15:09:20FAILED
  
 1) THE MAXIMUM FOOT CANDLES AT THE SITE BOUNDARY MAY
 NOT EXCEED 1 FOOTCANDLE. THE PHOTOMETRIC PLAN SHOWS
 VALUES EXCEEDING THIS ALONG THE SOUTHERN PROPERTY LINE.
  
 2) THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE
 THAT LIGHTING SHALL BE SCREENED TO REFLECT LIGHT OR
 GLARE AWAY FROM ADJACENT RIGHTS-OF-WAY. PLEASE PROVIDE
 INFORMATION AS TO HOW THIS WILL BE ACHIEVED ALONG 45TH
 STREET.
  
 3) THE SERVICE RACK SHALL BE SCREENED FROM VIEW FOR ITS
 FULL HEIGHT. PROVIDE THE HEIGHT OF THE SERVICE RACK ON
 THE PLANS AND OUTLINE HOW THE SCREENING WILL OCCUR. THE
 SCREENING SHALL BE IN PLACE PRIOR TO THE FINAL
 INSPECTION FOR THIS PERMIT. ANY REQUIRED PERMITS SHALL
 BE APPROVED PRIOR TO THE INSTALLATION OF THE SCREENING.
  
 4) POLE HEIGHT AND LOCATION MEETS ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.