Date Text
2014-11-05 15:36:345200 EAST AVENUE
 PERMIT #14110210
 INSTALL: 11/13/14
 EVENT: 11/15/14
 TEAR-DOWN: 11/17/14
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EVENT FLYER INDICATES A COOKING ACTIVITIES AND A
 BONFIRE. A SEPARATE PERMIT APPLICATION IS NEEDED FOR
 OPEN FLAME SUCH AS A BONFIRE. WHERE WILL THESE ITEMS
 TAKE PLACE ON THE SITE? WHAT TYPE OF FUELS ARE BEING
 USED? HOW WILL ASH AND EMBERS BE CONTAINED TO PREVENT
 FIRE SPREAD? RECREATIONAL FIRES SHALL NOT BE LOCATED
 WITHIN 25 FEET OF A STRUCTURE OR COMBUSTIBLE MATERIAL
 UNLESS CONTAINED IN AN APPROVED MANNER. CONDITIONS THAT
 COULD CAUSE A FIRE TO SPREAD TO WITHIN 25 FEET OF A
 STRUCTURE SHALL BE ELIMINATED PRIOR TO IGNITION. FIRE
 ATTENDANT: OPEN, RECREATIONAL, AND COOKING FIRES SHALL
 BE CONSTANTLY ATTENDED BY A COMPETENT PERSON UNTIL SUCH
 FIRE IS EXTINGUISHED.THIS PERSON SHALL HAVE A GARDEN
 HOSE CONNECTED TO THE WATER SUPPLY OR OTHER
 FIRE-EXTINGUISHING EQUIPMENT READILY AVAILABLE FOR USE.
  
 PROVIDE A FURNITURE/SEATING/TABLE PLAN.
  
 PLANS DO NOT INDICATE IF ANY OF THE TENTS HAVE
 SIDEWALLS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE