2014-12-17 16:45:48 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| BUILDING |
| |
| 1) THE DOOR SCHEDULE ON SHEET A-1 HAS SEVERAL MISTAKES. |
| EXTERIOR DOOR #1 DOES NOT HAVE A SIDELITE, DOOR #5 IS |
| AN IMPACT RATED EXTERIOR SLIDING GLASS DOOR, THE WIDTHS |
| OF DOORS #7 AND #8 ARE WIDER THAN THE CLOSETS THEY |
| SERVE, DOOR #6 IS A PAIR OF SWINGING DOORS AND THE ID |
| TAGS FOR THE CLOSET DOORS IN BEDROOMS #2 AND #3 ARE |
| MISSING FROM THE FLOOR PLAN. FBC 107.2.1 |
| |
| 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THE AWNING WINDOW ("D" ON SHEET A-1) THOSE PRODUCTS |
| WHICH ARE REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD. |
| |
| 3) THE PRODUCT APPROVALS FOR THE BORAL TILESEAL ( NOA |
| NO.12-0417.06 ) AND THE CAST-CRETE 8" LINTELS ( NOA NO. |
| 12-0209.13 ) HAVE BEEN SUPERSEDED. SUBMIT TWO SETS OF |
| CURRENT PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC |
| 107.3.4 |
| |
| 4) SPECIFY WHICH ONE OF THE TILES LISTED IN THE PRODUCT |
| APPROVAL WILL BE USED AND SPECIFY THE ATTACHMENT METHOD |
| THAT WILL BE USED. THE TILE PROFILE AND THE NUMBER AND |
| TYPE OF MECHANICAL FASTENERS OR ADHESIVE IS NEEDED TO |
| DETERMINE THAT THE REQUIRED WIND RESISTANCE IS MET. FBC |
| 107.2.1 & FBC-R905.3 NOTE: IF A TILE ADHESIVE IS USED, |
| SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD. |
| |
| 5) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS PLACEMENT |
| PLANS AND TRUSS DRAWINGS THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE STRUCTURAL ENGINEER FOR THE |
| PROJECT. FBC-R 802.1.6.1 |
| |
| |