2014-11-15 12:29:31***PROVISO****
 1) THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL. FAC SEC.604.3.1.
 2) THE REQUIRED 30 INCH X 48 INCH CLEAR FLOOR SPACE
 REQUIRED FOR THE DRINKING FOUNTAIN SHALL BE CENTERED ON
 THE INDIVIDUAL UNIT AND NOT ON BOTH UNITS. FAC 602.2.
 3) KNEE & TOE CLEARANCE FOR DRINKING FOUNTAIN SHALL
 COMPLY W/ FAC SEC. 305
  