Plan Review Notes For Permit 14110170 |
Permit Number |
14110170 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-12 15:55:15 | 12/12/2014 | | PROJECT: USI | | PERMIT#: 14110170 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION | | | | 1)SEE PERMIT NUMBER 14100308 FOR A LOAD CALCULATION TO | | ILLUSTRATE THE THE TOTAL CONNECTED LOAD ON THE EXISTING | | SERVICE PLUS THE ADDITION OF THE PROPOSED NEW LOAD TO | | TOTAL LESS THAN THE 1600AMP SERVICE MAIN. NEC 220.12, | | 220.14, 230.31 | | | | 2) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | 110.16, 110.22 | | | | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. NEC 110.9 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|