Plan Review Notes For Permit 14110155 |
Permit Number |
14110155 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-16 15:19:48 | PLAN DENIED | | 1) DON'T TIE FRESH AIR DAMPER INTO TIME CLOCK | | PER SECTION 503.2.5.4 FLORIDA ENERGY CODE 2010 | | 2) REFER TO SECTION 501.2.1 EXHAUST LOCATION | | EXHAUST OUTLETS. 2010 FBC (M) | | 3) PROVIDE THE BOLT SIZE USED FOR ANCHORING | | CONDENSER STAND TO ROOF. | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 651-805-6676 |
|