Plan Review Notes For Permit 14110155 |
Permit Number |
14110155 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-03 09:23:11 | APPROVED WITH EXCEPTION: CORRECT THE CONFLICT ON PLANS. | | SHEET E-3 INDICATES A #6 WIRE FEEDING PANE LVA FROM | | PANEL LV, HOWEVER SHEET E-4 INDICATES A # 8WIRE BEING | | FED FROM A 60AMP BREAKER IN PANEL LV FEEDING PANEL LVA. | | | | SHEET E-4 | | REPLACE EITHER THE PROPOSED 3PH60AMP OCPD FEEDING PANEL | | LVA, #37,39,41, WITH A 3PH 50AMP OCPD *OR* REPLACE THE | | #8THWN CU WIRE SHOWN ON THE PANEL SCHEDULE WITH #6THWN | | CU AS INDICATED ON THE RISER DIAGRAM SHT E-3 IF THE | | 60AMP OCPD FEEDING PANEL LVA IS PROPOSED TO REMAIN. | | | | SHEET E-3 | | MAKE THE RISER MATCH THE PANEL SCHEDULE. |
|