Plan Review Notes
Plan Review Notes For Permit 14110155
Permit Number 14110155
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-03 09:23:11APPROVED WITH EXCEPTION: CORRECT THE CONFLICT ON PLANS.
 SHEET E-3 INDICATES A #6 WIRE FEEDING PANE LVA FROM
 PANEL LV, HOWEVER SHEET E-4 INDICATES A # 8WIRE BEING
 FED FROM A 60AMP BREAKER IN PANEL LV FEEDING PANEL LVA.
  
 SHEET E-4
 REPLACE EITHER THE PROPOSED 3PH60AMP OCPD FEEDING PANEL
 LVA, #37,39,41, WITH A 3PH 50AMP OCPD *OR* REPLACE THE
 #8THWN CU WIRE SHOWN ON THE PANEL SCHEDULE WITH #6THWN
 CU AS INDICATED ON THE RISER DIAGRAM SHT E-3 IF THE
 60AMP OCPD FEEDING PANEL LVA IS PROPOSED TO REMAIN.
  
 SHEET E-3
 MAKE THE RISER MATCH THE PANEL SCHEDULE.