2014-11-26 09:17:05 | BUILDING PLAN REVIEW |
| PERMIT: 14110155 |
| ADD: 700 S ROSEMARY AVE. SUITE 140 |
| CONT: CHANDLER CONSTRUCTION |
| TEL: (561)791-6934 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. NOV. 26/ 2014 |
| |
| NOTICE GREASE DUCTS WILL REQUIRE A SEPARATE PERMIT & |
| REVIEW. |
| |
| ACTION: BUILDING PROVISO |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| |
| 1) SHEET A2.2 SHOWS A GREASE DUCT WITH A 2 HR. DUCT |
| WRAP THAT WILL BE INCOMPLIANCE WITH FBC-M ASTM E 2336. |
| NO LITERATURE HAS BEEN PROVIDED. THE 2010 FBC-B 708.2 |
| EXCEPTION #4 STATES GREASE DUCTS SHALL BE PROTECTED IN |
| ACCORDANCE WITH THE FBC-MECHANICAL. PLEASE PROVIDE THE |
| LITERATURE SHOWING COMPLIANCE. |
| |
| 2) THERE IS A DISCREPANCY IN THE PLANS AND HOW THE |
| ACTUAL FIELD CONDITION OF THE 2 HR. DUCT WRAP, PLEASE |
| REVIEW 2010 FBC-M 506.3.10.2. THE SURFACE OF THE DUCT |
| SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM THE |
| POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET |
| TERMINAL. THE PLANS, TYPICAL CURB DETAIL ON A2.1 & |
| SECTION THROUGH THE GREASE DUCT CHASE, A2.2 SHOW THE |
| DUCT WRAP CONTINUING TO THE ROOF TOP HOOD EXHAUST FAN. |
| IN REALITY THE DUCT WRAP STOPS AT THE TOP OF THE HOOD |
| EXHAUST DUCT ROOF TOP CURB, PLEASE SHOW THE OUTLET |
| TERMINAL HOW IT WILL BE MADE WATER TIGHT, AND HOW IT |
| WILL BE ATTACHED TO THE ROOF TOP CURB. PLEASE ALLOW IN |
| SIZING FOR THE CURB 2 LAYERS OF DUCT WRAP TO CONTINUE |
| TO THE TOP OF THE ROOF CURB. |
| |
| 3A) SHEET A-8.2 DETAIL B SHOWS NEW GLAZING IN THE |
| STOREFRONT, THESE PRODUCT APPROVALS ARE TO BE REVIEWED |
| AS A DEFERRED SUBMITTAL UNDER 107.3.4.2 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION,. |
| |
| 3B) ALSO NOTE THAT THE DESIGNER OF RECORD IS TO HAVE |
| REVIEWED AND APPROVED THE SUBMITTED PRODUCT APPROVALS |
| WITH THEIR SHOP DRAWING STAMP OF APPROVAL. |
| 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |