2015-01-06 08:34:38 | PLAN REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| BUILDING |
| |
| 1) COMPLIED |
| |
| 2) COMPLIED |
| |
| 3) THE PRODUCT APPROVALS FOR THE BORAL TILESEAL ( NOA |
| NO.12-0417.06 ) AND THE CAST-CRETE 8" LINTELS ( NOA NO. |
| 12-0209.13 ) HAVE BEEN SUPERSEDED. SUBMIT TWO SETS OF |
| CURRENT PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC |
| 107.3.4 (REPEAT COMMENT) THE SUPERSEDED NOAS WERE |
| SUBMITTED AGAIN. THE CURRENT NOA FOR THE BORAL TILE |
| SEAL IS NOA NO. 13-1113.05 AND THE ONE FOR THE |
| CAST-CRETE 8" LINTELS IS NOA NO. 14-0903.02. THE |
| FOLLOWING IS THE LINK TO THE MIAMI-DADE PRODUCT |
| APPROVAL WEBSITE: |
| HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP |
| |
| 4) SPECIFY WHICH ONE OF THE TILES LISTED IN THE PRODUCT |
| APPROVAL WILL BE USED AND SPECIFY THE ATTACHMENT METHOD |
| THAT WILL BE USED. THE TILE PROFILE AND THE NUMBER AND |
| TYPE OF MECHANICAL FASTENERS OR ADHESIVE IS NEEDED TO |
| DETERMINE THAT THE REQUIRED WIND RESISTANCE IS MET. FBC |
| 107.2.1 & FBC-R905.3 NOTE: IF A TILE ADHESIVE IS USED, |
| SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD. (REPEAT COMMENT) PRODUCT APPROVALS FOR MALIBU |
| CONCRETE TILE (NOA NO. 11-0321.01) WERE SUBMITTED, |
| HOWEVER, THE ATTACHMENT INFORMATION WAS NOT PROVIDED. |
| |
| 5) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS PLACEMENT |
| PLANS AND TRUSS DRAWINGS THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE STRUCTURAL ENGINEER FOR THE |
| PROJECT. FBC-R 802.1.6.1 (REPEAT COMMENT) |
| |
| |
| |
| |