Date |
Text |
2014-11-04 13:30:26 | BUILDING PLAN REVIEW |
| PERMIT: 14110062 |
| ADD: 1901 S DIXIE HWY. |
| CONT: SISCA CONSTRUCTION |
| TEL: (561)228-7503 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. NOV. 04/ 2014 |
| ACTION: DENIED |
| |
| 1) 2010 FBC-B 3303.1 CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS MUST BE SUBMITTED WHEN REQUIRED |
| BY THE BUILDING OFFICIAL. WHERE SUCH INFORMATION IS |
| REQUIRED, NO WORK SHALL BE DONE UNTIL SUCH CONSTRUCTION |
| DOCUMENTS OR SCHEDULE, OR BOTH, ARE APPROVED. |
| |
| ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS |
| IS TO ADVISE YOU OF THE OWNERS OR OPERATOR???S |
| RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL |
| ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S. |
| AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- |
| ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION |
| TO THE DEPARTMENT OF ENVIROMENTAL PROTECTION PRIOR TO: |
| * DEMOLITION OF ALL REGULATED STRUCTURES; * MOST |
| RENOVATION ACTIVITIES IN REGULATED STRUCTURES WHERE |
| ASBESTOS IS DISTURBED OR REMOVED. NON-COMPLIANCE MAY |
| RESULT IN SEVERE MONETARY PENALTY. |
| |
| 2) SHEET D1.0 NOTES DEMOLITION KEY NOTES 3 & 4 INDICATE |
| THE REMOVAL OF WINDOWS AND DOORS. THE DEMOLITION NOT # |
| 11 THE CONTRACTOR IS TO SECURE THE |
| TENANT SPACE AT ALL TIMES. HOW WILL THIS BE |
| ACCOMPLISHED. SINCE THERE ARE NO PLANS SUGGESTING A |
| TENANT BUILD OUT WILL BE PERMITTED, THIS IS A SHELL OF |
| THE BUILDING. THE BUILDING HAD BEEN DESIGNED AS A |
| ENCLOSED BUILDING. WITH THE WINDOWS AND DOORS REMOVED |
| PLEASE PROVIDE HOW THE CONTRACTOR IS GOING TO ENSURE |
| THIS STRUCTURE TO BE SECURED IN A HIGH WIND EVENT SINCE |
| THE BUILDING WAS NEVER DESIGNED AS A OPEN OR PARTIALLY |
| OPEN BUILDING. 2010 FBC-B |
| 1609.1 APPLICATIONS. BUILDINGS, STRUCTURES AND PARTS |
| THEREOF SHALL BE DESIGNED TO WITHSTAND THE MINIMUM WIND |
| LOADS PRESCRIBED HEREIN. |
| |
| 3) 2010 FBC-B 3303.6 UTILITY CONNECTIONS. SERVICE |
| UTILITY CONNECTIONS SHALL BE DISCONTINUED AND CAPPED IN |
| ACCORDANCE WITH THE APPROVED RULES AND THE REQUIREMENTS |
| OF THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 4) NOTE, NO ACTION REQUIRED!!! SINCE THIS WILL IN |
| EFFECT BE JUST A SHELL BUILDING WITH NO OCCUPANCY, THE |
| CERTIFICATE OF OCCUPANCY WILL BE REVOKED AND THE TENANT |
| BUILD-OUT WOULD REQUIRE A NEW CERTIFICATE OF OCCUPANY. |
| 2010 EXISTING BUILDING CODE901.4 CERTIFICATE OF |
| OCCUPANCY REQUIRED. A CERTIFICATE OF OCCUPANCY SHALL BE |
| ISSUED WHERE A CHANGE OF OCCUPANCY OCCURS THAT RESULTS |
| IN A DIFFERENT OCCUPANCY CLASSIFICATION AS DETERMINED |
| BY THE FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |