Date Text
2014-11-17 05:16:221) SHT.A-1 - H.C. LAVATORY DETAIL - THE PLAN VIEW OF
 THE TOILET ROOM SHOWS A 48" X 56 " CLEARANCE FOR THE
 WATER CLOSET. SEC. 603.3.1. OF THE 2010 FL.
 ACCESSIBILITY CODE REQUIRES A CLEARANCE OF 56" MINIMUM
 X 60 " MINIMUM. SHOW THE REQUIRED CLEARANCE ON THE
 FLOOR PLAN.
 2) THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR THE WATER CLOSET PER FAC SEC.603.2.3. SEE
 THE EXCEPTIONS FOR APPLICABILITY.
 3) SHT. A-1 -THE ENLARGED FLOOR PLAN OF TOILET ROOM
 SHOWS THE TOILET ROOM DOOR SWINGING INTO THE ROOM AND
 THE FLOOR PLAN ON SHT. A-1 & A-2 SHOW THE DOOR SWINGING
 OUT. CLARIFY.
 4) THE SINK IN THE COFFEE ROOM SHALL COMPLY WITH THE
 2010 FAC SEC. 212.3 AND 606.2.
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 INSTA- HOT.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SHT. A-1 NOTES THE WATER CLOEST IN THE COFFEE ROOM
 TO BE CAPPED BUT THE RISER DIAGRAM ON SHT. A-2 STATES
 "FUTURE WATER CLOSET." WHICH IS IT?
 7) SHOW THE CLEAR FLOOR SPACE FOR THE SINK IN THE
 COFFEE ROOM PER THE 2010 FAC SEC.606.2. THE CLEAR FLOOR
 SPACE SHALL BE CENTERED ON THE FIXTURE,
 8) THE SIZE OF THE VENT (2 1/2" ) FOR THE DRINKING
 FOUNTAIN AND SINK IS NOT A CONVENTIONAL PIPE SIZE.
 CLARIFY.
 9) SUBMIT A WATER RISER FOR THE CHANGES MADE TO THE
 PLUMBING SYSTEM PER THE WPB AMEND, TO 2010 FBC SEC.
 107.3.5.1.3.
  