Plan Review Notes
Plan Review Notes For Permit 14101066
Permit Number 14101066
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-11-07 11:05:18THIS PLAN WAS REVIEWED AND FAILED WITH THE FOLLOWING
 COMMENTS;
  
 PERMIT# 14101066
  
 PROVIDE LEGIBLE BATTERY CALCULATIONS.
  
 ALL DUCT DETECTORS TO INITIATE GENERAL ALARM.
  
 REMOTE PULL IS NOT PROVIDED AT REQUIRED EXIT SOUTH WALL
 OF NON AC STORAGE.
  
 CEILING HEIGHT IS NOT PROVIDED, ALSO CANDELA IS NOT
 PROVIDED.
  
 ROY LINDOW
 WEST PALM BEACH FIRE
  