Plan Review Notes For Permit 14101066 |
Permit Number |
14101066 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-11-07 11:05:18 | THIS PLAN WAS REVIEWED AND FAILED WITH THE FOLLOWING | | COMMENTS; | | | | PERMIT# 14101066 | | | | PROVIDE LEGIBLE BATTERY CALCULATIONS. | | | | ALL DUCT DETECTORS TO INITIATE GENERAL ALARM. | | | | REMOTE PULL IS NOT PROVIDED AT REQUIRED EXIT SOUTH WALL | | OF NON AC STORAGE. | | | | CEILING HEIGHT IS NOT PROVIDED, ALSO CANDELA IS NOT | | PROVIDED. | | | | ROY LINDOW | | WEST PALM BEACH FIRE | | |
|