2014-11-15 13:06:49 | 11/15/2014 |
| PROJECT: COASTAL WAREHOUSE |
| PERMIT#: 14101066 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE INFORMATION ON THE PLAN FOR THE METHODS AND |
| MATERIALS PROPOSED FOR THE INSTALLATION OF THE SYSTEM. |
| THE FLOOR PLAN INDICATE A CONNECTION FROM A FEW DEVICES |
| TO OTHER DEVICES BUT DIAGRAM IS INCOMPLETE. PROVIDE A |
| COMPLETE AND DETAILED PLAN OF THE INSTALLATION |
| INCLUDING THE COMPLETE INTERCONNECTION BETWEEN DEVICES |
| AND THE TERMINATION TO THE FACP ALL IN ACCORDANCE WITH |
| THE REQUIREMENTS IN NEC 760. |
| |
| 2) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL ON THE |
| FLOOR PLAN ALONG WITH AN ELECTRICAL PANEL SCHEDULE |
| INCLUDING THE FACP CIRCUIT INDICATING THAT IT WILL BE |
| INSTALLED WITH A LOCK ON DEVICE AND BE IDENTIFIED WITH |
| PERMANENT RED MARKING. |
| |
| 3) ALL INFORMATION ON THE PLANS INCLUDING THE |
| SPECIFICATIONS AND MANUFACTURER PRODUCT INFORMATION |
| DATA SHALL BE LEGIGBLE. THE BATTERY CALCULATIONS AND |
| CIRCUIT DETAIL CHARTS ARE NOT LEGIBLE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |