2014-11-05 10:22:11 | BUILDING PLAN REVIEW |
| PERMIT:14101060 |
| ADD: 800 HANK AARON DRIVE |
| CONT: KAST |
| TEL: (561) 346-4994 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. NOV. 05/2014 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES WORK UNDER THIS |
| PERMIT TO BE LOCATED AT 800 HANK AARON DRIVE. KAST |
| CONSTRUCTION SUBMITTED ADDRESSES TO BE USED BEFORE THE |
| BUILDING PERMIT WERE ISSUED. THE SITE ADDRESS TO BE |
| USED IS NOW 1590 CAMERON SAMUEL LN. PLEASE MAKE |
| CORRECTIONS TO THE PERMIT APPLICATION AND PLANS UNLESS |
| THE CONTRACTOR IS LOOKING FOR A ADDRESS FOR THIS UNIT |
| ONLY, THEN A NEW ADDRESS WILL BE REQUIRED. |
| CONTACT: SCOTT ALEF 494-1094. |
| |
| 2) THE STATE APPROVED PLANS HAVE BEEN MINIATURIZED |
| BEYOND 1/8 INCH EQUALLS 1 FOOT. THE PLANS ARE ELIGIBLE. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1.4 QUALITY OF |
| BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. |
| |
| 3) THE ANCHORING PLAN IS A COPY, THE STATE APPROVED |
| PLANS DO NOT INCLUDE THE FOUNDATION PLAN. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G16.003 ARCHITECTS |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| |
| 4) THERE IS NO INDICATION IF THIS IS A TEMPORARY |
| STRURCTURE, LESS THAN 180 DAYS ON THE PERMIT |
| APPLICATION. MODULAR BUILDINGS THAT ARE IN PLACE OVER |
| 180 DAYS ARE NOT TEMPORARY AND WOULD NEED TO MEET THIS |
| BUILDING REQUIREMENT. 2010 FBC-B 1809.4 DEPTH AND WIDTH |
| OF FOOTINGS. |
| THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED |
| GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE |
| APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL |
| ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL |
| BE 12 INCHES (305 MM). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |