2014-12-08 12:13:25 | 12/8/2014 |
| PROJECT: TENANT IMPROVEMENTS, PP STE1000 |
| PERMIT#: 14101018 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION |
| |
| 1) NEC 240.4 CLARIFICATION REQUIRED. SHEET E1.1 |
| INDICATES A TWO POLE 30AMP CIRCUIT #27/29 WITH TWO #8CU |
| FEEDING CU-10E-9 LOCATED ON THE ROOF. HOWEVER, |
| ELECTRICAL KEYNOTE 1 ON THE SAME SHEET STATES CONNECT |
| CU-10E-9 TO AHU-10E-9 USING TWO #12 1#12G IN 1/2" |
| CONDUIT. PLEASE INDICATE WHERE, HOW AND WITH WHAT TYPE, |
| SIZE AND STYLE OF OCPD PROTECT THE #12 CIRCUIT FROM THE |
| CU-10E-9 TO AHU-10E-9. |
| |
| 2) NEC 314.27(C ) BOXES LISTED SPECIFICALLY FOR THIS |
| APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED IN |
| THE FLOOR. PROVIDE MANUFACTURER'S SPECIFICATION DATA |
| SHEETS FOR THE OUTLETS LOCATED IN THE FLOOR. |
| A. NEC 300.21 PROVIDE A FIRE STOP DETAIL FOR ALL WALL |
| AND FLOOR PENETRATIONS OF FIRE RATED ASSEMBLIES. |
| B. FBC 713.4 PENETRATIONS OF A FLOOR, FLOOR/CEILING |
| ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING |
| ASSEMBLY NOT REQUIRED TO BE ENCLOSED IN A SHAFT BY |
| SECTION 708.2 SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTIONS 713.4.1 THROUGH 713.4.2.2. |
| |
| 3) FBC 505.2.2 EX 4.SPACES WHERE AN AUTOMATIC SHUTOFF |
| WOULD ENDANGER OCCUPANT SAFETY OR SECURITY. ELECTRICAL |
| ROOM LIGHTS SHOULD NOT BE CONNECTED TO A MOTION SENSOR |
| SWITCH. |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, |
| SECURITY, CCTV, NETWORK, DATA, COMMUNICATION, SITE |
| LIGHTING, AND GENERATORS. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |