Plan Review Notes
Plan Review Notes For Permit 14100874
Permit Number 14100874
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-09 12:28:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHOP DRAWING REVIEW BY DESIGNER OF RECORD REQUIRED,
 SEE FBC 107, FAC61G15-30, 18. THIS MAY BE DONE WITH A
 LETTER OR SHOP DRAWING REVIEW STAMP.
  
 2. SEE FAC61G15-23 FOR THE FORMAT FOR CALCULATIONS
 PREPARED BY AN ENGINEER. EITHER AN INDEX SHEET WITH ALL
 REQUIRED INFORMATION IS TO BE USED, OR EACH SHEET
 SIGNED, SEALED, AND DATED WITH A TITLE BLOCK.
  
 3. SHEET E1.03 MAKES REFERENCE TO A SOILS REPORT.
 PLEASE PROVIDE A COPY.
  
 4. I WAS UNABLE TO LOCATE EXPOSURE CLASSIFICATION IN
 THE CALCULATIONS OR ON SHEET E1.03. IT APPEARS THAT
 THIS IS LOCATED IN EXPOSURE C, BUT PLEASE HAVE ENGINEER
 CONFIRM THAT THIS IS NOT EXPOSURE D (DUE TO PROXIMITY
 TO CLEAR LAKE), FBC 1603.1.4.
  
  