Plan Review Notes For Permit 14100844 |
Permit Number |
14100844 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-31 05:34:13 | *****NOTE**** | | SEPARATE PERMIT REQ. FOR GAS. | | TKL. | | | | | | | | | | WPB AMEND. TO 2010 FBC SEC.107.2.1. | | 1) SUBMIT 2 COPIES OF A GAS RISER FOR REVIEW. | | 2) SUBMIT 2 COPIES OF MANUF. SPECS AND INSTALLATION | | INSTRUCTIONS FOR THE POOL HEATER. HEATER SHALL BE | | LISTED AND LABELED PER THE FL. GAS CODE SEC. 301.3. | | 3) SUBMIT 2 COPIES OF THE APPLICABLE GAS SIZING TABLE | | FROM THE FL. GAS CODE FOR THE TYPE OF SYSTEM & TYPE OF | | PIPE BEING USED. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|