2014-11-21 10:49:30 | 11/21/2014 |
| PROJECT: BEDROOM WALL |
| PERMIT#: 14100830 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| 314 AND 315. PROVIDE OR VERIFY THE REQUIRED SMOKE |
| DETECTORS IN THE LOCATIONS REQUIRED BY THE FBC-R314, |
| 315 |
| |
| 2) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| OUTLET.). NEC 210.52(A)(1) IT APPEARS AS THOUGH AN |
| ADDITIONAL OUTLET IS REQUIRED IN THE NEW PARTITION. |
| EITHER INDICATE A NEW OUTLET WILL BE INSTALLED OR |
| INDICATE HOW THE EXISTING OUTLETS COMPLY WITH THE NEC |
| 210.52(A)(1) |
| |
| 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 4) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET |
| SHALL BE INSTALLED IN EVERY HABITABLE ROOM AND |
| BATHROOM. CLARIFY HOW THE INTENT OF NEC 210.70(A)(1) |
| WILL BE MET. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |