2014-11-06 11:36:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE |
| FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND |
| COMPLIANCE. |
| |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| THE SUBMITTED PLAN LACKS THE REQUIRED DETAIL REGARDING |
| LIFE SAFETY SYSTEMS DEVICE LOCATIONS, INCLUDING BUT NOT |
| LIMITED TO, SMOKE DETECTORS, SPRINKLER HEADS, AND FIRE |
| ALARM DEVICES; BOTH EXISTING AND PROPOSED. |
| |
| WHAT IS THE PROPOSED OCCUPANCY TYPE, RESIDENTIAL, |
| BUSINESS OR OTHER? |
| |
| THE ROOMS ARE NOT LABELED AND IS THE DRAWING THE ENTIRE |
| SPACE OR JUST A PORTION OF A LARGER SPACE? |
| |
| A LIFE SAFETY PLAN IS NOT PROVIDED, INDICATING ALL |
| OCCUPANCY LOADS, EXIT PATHS, EXITS SIGNS(IF REQUIRED |
| FOR BUSINESS), EMERGENCY LIGHTS(IF REQUIRED FOR |
| BUSINESS) AND EXIT DOORS. |
| |
| PLEASE ALSO REVIEW OTHER DEPARTMENT COMMENTS. |