2014-11-14 16:32:28 | 11/14/2014 |
| PROJECT: BEDROOM WALL |
| PERMIT#: 14100830 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) MINIMUM ELECTRICAL PLAN REVIEW CRITERIA SHALL |
| INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: WIRING, |
| SERVICES, FEEDERS AND BRANCH CIRCUITS, OVERCURRENT |
| PROTECTION, GFCIS, GROUNDING, WIRING METHODS AND |
| MATERIALS, WPB AMENDMENTS TO FBC 107.3.5.1.2 |
| |
| 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. |
| WPB AMENDMENTS TO FBC 107.2.1 |
| |
| 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| 314 AND 315 |
| |
| 4) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| OUTLET. 210.52(A)(1) |
| |
| 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |