2014-11-07 18:02:24STAIRCASE RAILING SUBMITTAL, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PLANS SUBMITTED NEED TO HAVE THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 2- RAILINGS NEED TO BE DESIGNED TO THE LIVE LOADS
 REQUIRED BY TABLE R301.5 OF 2010 FBC-RESIDENTIAL
 (IMPORTANT: SEE NOTES D AND H). PERSON RESPONSIBLE FOR
 THE DESIGN TO PROVIDE SPECIFICATIONS SHOWING THAT THE
 RAILING WAS DESIGNED TO THOSE LOADS.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 STRUCTURAL CONNECTIONS: POSTS TO FLOOR AND STAIRWAY,
 POST TO ROUND CAP, ROUND CAP TO WALL, ETC. SEC. R301.1
 OF 2010 FBC-RESIDENTIAL.
  
 4- A) ARCHITECT OF RECORD TO REVIEW AND APPROVE THIS
 SUBMITTAL. SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 B) ARCHITECT TO PLACE REVIEW STAMP ON THE FRONT OF THE
 DRAWING NOT ON THE BACK. THIS IS REQUIRED FOR PROPER
 RECORD RETENTION. STAMPS ON BACK OF THE DRAWINGS DON'T
 GET SCANNED FOR RECORD RETENTION. SEC. 107.2.1.4 OF
 CITY AMENDMENTS TO FBC.
  
 5- ADDED ONE PAGE FOR THE STAIRWAY RAILING FOR THE
 REVISION REVIEW. OWES $51.50 UNDER THIS REVISION
 #14100785.
  
  