2014-10-28 08:02:23 | BUILDING REVIEW COMMENTS TO SUBMITTAL ADDRESSING |
| PROVISO DATED 8/7/14: |
| |
| 1- COMMENT #1: |
| (A) OK. NO ROOF WORK. |
| |
| (B) NOT OK. SEE COMMENTS BELOW: |
| (1) DRAWING S-100 SUBMITTED NEEDS ENGINEER ORIGINAL |
| SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. |
| (2) FLORIDA PRODUCT APPROVAL FL 474 SPECIFIED ON THE |
| CONNECTOR'S SCHEDULE ON SHEET S-100 IS NOT CURRENT. |
| NEED PRODUCT APPROVAL NUMBER FOR CURRENT CODE EDITION |
| 2010 FBC. ALSO, THERE IS NOT FLORIDA PRODUCT APPROVAL |
| NUMBER OR NOA NUMBER FOR TSP CONNECTOR. REVISE AS |
| REQUIRED. |
| |
| (C) OK. CURRENT MULLION NOA SUBMITTED. |
| |
| (D) OK. ROUND CASEMENT WINDOW SUBMITTED WITH FIXED |
| CASEMENT WINDOW NOA. |
| |
| (E) OK. |
| |
| (F) OK. |
| |
| 2- NOT OK. ALL PRODUCT APPROVALS NEED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. THE |
| ONLY PRODUCT APPROVAL THAT WAS SUBMITTED AT HIS TIME |
| WAS THE WINDOW MULLIONS AND WAS NOT REVIEWED BY THE |
| DESIGNER OF RECORD. |
| |
| 3- ITEM #3. ACCORDING TO CONTRACTOR'S RE-SUBMITTAL |
| LETTER, CONTRACTOR WILL DELIVER DRAWINGS/SPECS THE WEEK |
| OF 10/27/14. NOT SUBMITTED YET. |
| |
| 4- BALCONY GUARDRAILS DETAILS SUBMITTED NEED THE |
| FOLLOWING: |
| A) PROVIDE THE DESIGN INFORMATION AS REQUIRED BY TABLE |
| R301.5 OF 2010 FBC. |
| B) PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 |
| OF CITY AMENDMENTS TO FBC. |
| C) DESIGNER OF RECORD TO REVIEW AND APPROVE THE BALCONY |
| GUARDRAILS DRAWINGS PRIOR TO SUBMITTAL TO THIS OFFICE. |
| SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| |
| 5- ENGINEER RESPONSIBLE FOR SHEET S-100 TO PROVIDE |
| ORIGINAL SIGNATURE AS REQUIRED BY CHAPTER 471 F. ST. |
| |
| 6- NOT OK. THERE WERE NO REVISED STRUCTURAL BUCK |
| DETAILS SUBMITTED. SEC. R612.10.2.1 OF 2010 FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |
| |
| |
| |
| |
| SEE ORIGINAL PROVISO COMMENTS BELOW FOR REFERENCE: |
| |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS, DETAILS AND SPECIFICATIONS. |
| C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| D) ROUND CASEMENT WINDOW AS SHOWN ON PLANS. |
| E) NEW ALUMINUM CASEMENT NOA 12-0216.04 WAS SUBMITTED. |
| NEED TO PROVIDE TWO COPIES. |
| F) NEW FRENCH DOORS FLORIDA PRODUCT APPROVAL FL14504 |
| WAS SUBMITTED. NEED TO PROVIDE TWO COPIES. |
| 2- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT |
| APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS. |
| 3- SHEET A-2: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR INTERIOR HANDRAIL TO BE REPLACED. |
| TABLE R301.5 AND SEC. R311.7.7. |
| 4- SHEET A-4: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY. TABLE |
| R301.5 AND SEC. R312. |
| 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON |
| FIRST FLOOR. SEC. R301. |
| 6- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK |
| DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR |
| FRAME. SEC. R612.10.2.1. |