Plan Review Notes
Plan Review Notes For Permit 14100783
Permit Number 14100783
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-17 07:57:231.) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12(F)
  
 2.) OUTLETS INSTALLED OUTDOORS OR WITHIN 6' OF A SINK
 SHALL BE GFCI PROTECTED. NEC 210.8(B)(4)
 A.) GFI OUTLETS INSTALLED IN DAMP OR WET LOCATIONS
 SHALL ALSO BE THE WEATHER RESISTANT TYPE. NEC
 406.8(B)(1)