Notes |
Date |
Text |
2014-11-14 16:33:44 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. DESIGN PRESSURE FOR ZONE 3 IS THE SAME AS ZONE 2. | | USE OF ZONE 2 PRESSURES FOR CORNERS REQUIRES A PARAPET | | ON ALL FOUR SIDES. AERIAL PHOTOGRAPHS APPEAR TO SHOW A | | FLAT ROOF OVER THE PORCH AT THE REAR OF THE HOUSE, NO | | PARAPET. PLEASE PROVIDE INFORMATION REGARDING PARAPET | | AND HEIGHT, FBC 2010 RESIDENTIAL 301. | | | | 2. ENGINEER TO CLARIFY MEANING OF "ZONE 2 & 2' " AND | | "ZONE 3 & 3' ". FBC 107 | | |
|