Plan Review Notes
Plan Review Notes For Permit 14100751
Permit Number 14100751
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-24 13:22:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN DOES NOT INDICATE WHETHER EXIT DOORS OR ONLY
 WINDOWS ARE TO BE COVERED BY SHUTTERS. REVISE PLAN TO
 INDICATE.
  
 2. IF DOORS ARE AFFECTED, PROVIDE A FLOOR PLAN SHOWING
 EXITING INCLUDING ALL EXITS, OVERALL BUILDING SIZE,
 BASIC FLOOR PLAN. THIS MAY BE SENT FOR PRELMINIARY
 REVIEW VIA EMAIL.
  
 SEE FBC 1003.6. HURRICANE SHUTTERS OVER EXIT DOORS ARE
 CONSIDERED ON A CASE BY CASE BASIS AS THERE IS NO
 PROVISION IN THE BUILDING CODE FOR THIS APPLICATION.
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.4.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  