2014-11-25 16:57:42 | RESIDENTIAL (R3) SCREEN ENCLOSURE BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- SCREEN ENCLOSURE SITE SPECIFIC LAYOUT. PROVIDE THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN AS REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS TO |
| FBC. |
| ***NOTE: SEE ZONING COMMENTS. SCREEN ENCLOSURE |
| DIMENIOSN MAY NEED TO BE REVISED. |
| |
| 2- SCREEN ENCLOSURE FLOOR PLAN AND ELEVATIONS SHOWN ON |
| THE SITE SPECIFIC LAYOUT DON'T MATCH. CLARIFY WHY THERE |
| IS A 2X9 BEAM SHOWN ON THE ELEVATIONS. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- CLEARLY IDENTIFY SIZE OF ALL FRAMING MEMBERS. SCREEN |
| ENCLOSURE LAYOUT SHOW DIFFERENT PURLIN SIZES, DIFFERENT |
| K-BRACING SIZES, DIFFERENT EAVE RAIL SIZES, ETC. REVISE |
| AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO |
| FBC. |
| |
| 4- PROVIDE DETAILS FOR THE 5" SUPER GUTTER CONNECTION. |
| SEC. 107.2.1 CITY AMENDMENTS TO FBC. SEC. R301.1 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 5- ACCORDING TO TABLE 101(F)11 SUBMITTED THE ALLOWABLE |
| SPAN FOR THE 2X9 BEAM IS 19'-11". THE ACTUAL BEAM SPAN |
| SHOWN ON THE SCREEN ENCLOSURE LAYOUT IS 20'-7". REVISE |
| AS REQUIRED TO COMPLY. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 6- ACCORDING TO TABLE 102F SUBMITTED THE ALLOWABLE SPAN |
| FOR PURLINS FOR THE 2X7 PURLIN IS 6'-10". THE ACTUAL |
| PURLIN SPAN SHOWN ON THE SCREEN ENCLOSURE LAYOUT IS |
| 7'-3 5/8". REVISE AS REQUIRED TO COMPLY. SEC. R301.1 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 7- ACCORDING TO TABLE 105 SUBMITTED THE ALLOWABLE POST |
| HEIGHT FOR 3/8" CONCRETE FASTENERS IS 7.2'. THIS |
| DOESN'T MATCH THE POST SPAN SHOWN ON PLANS . REVISE AS |
| REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE SIZE OF EXISTING FOOTING. SEC. R301.1 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 9-PROVIDE ONLY THE DETAILS AND TABLES THAT APPLY TO |
| THIS PROJECT. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |