2014-11-25 18:46:55 | RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- DESIGNER OF RECORD TO PROVIDE NAME AND SIGNATURE ON |
| THE SITE SPECIFIC LAYOUT AS REQUIRED BY SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. |
| ***NOTE: SCREEN ENCLOSURE DIMENSIONS MAY NEED TO BE |
| REVISED. SEE ZONING COMMENTS. |
| |
| 2- CLARIFY SCREEN ENCLOSURE SITE SPECIFIC DRAWINGS. IS |
| THIS A FLAT ROOF SCREEN ENCLOSURE OR PITCHED ROOF?. IS |
| THERE A 2X9 BEAM OR 3X3 EAVE RAIL?. PLANS ARE NOT |
| CLEAR. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS |
| TO FBC. |
| |
| 3- PROVIDE CORRECT TABLE FOR THE ALLOWABLE BEAM SPAN TO |
| MATCH PLANS. IT LOOKS LIKE THIS IS A FLAT ROOF SCREEN |
| ENCLOSURE, NOT PITCHED. COORDINATE WITH ITEM #2 ABOVE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- PROVIDE ONLY THE DETAILS AND TABLES THAT APPLY TO |
| THIS PROJECT TO AVOID DISCREPANCIES OR CONFLICTS. SEC. |
| 107.2.1 CITY AMENDMENTS |
| |
| 5- THE ALLOWABLE POST HEIGHT FOR 3/8 CONCRETE FASTENERS |
| ON TABLE 105 SUBMITTED IS 7.7'. THIS HEIGHT DOESN'T |
| REFLECT PLANS. REVISE AS REQUIRED TO COMPLY. SEC. |
| R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 6- ALLOWABLE BEAM SPAM FOR RIBBON FOOTINGS TABLE 111 |
| SUBMITTED IS FOR EXPOSURE "B". REVISE AS REQUIRED. |
| HOUSE IS LOCATED IN EXPOSURE "C". SEC. R301 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |