2014-11-26 11:39:29 | RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE THE |
| NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| 2- PROVIDE DETAILS FOR THE 5" SUPPER GUTTER |
| CONNECTIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 3- THE ALLOWABLE SPAN FOR PURLINS TABLE 102F SUBMITTED |
| IS 4'-10". THIS DOESN'T REFLECT SPAN SHOWN ON PLANS. |
| REVISE AS REQUIRED TO COMPLY. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 4- REVISE ALLOWABLE POST/COLUMN SPAN CIRCLED WITH RED |
| INK ON TABLE 103F SUBMITTED. THE SPACING FOR SIDE WALL |
| POSTS IS NOT 6'-6". SEE PLANS AND REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 5- REVISE ALLOWABLE SPAN FOR GIRTS OR CHAIR RAILS |
| CIRCLED WITH RED INK ON TABLE 204F SUBMITTED. THE |
| SPACING IS NOT 4'-0". SEE PLANS AND REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 6- ALLOWABLE POST HEIGHT FOR 3/8" CONCRETE FASTENERS ON |
| TABLE 105 SUBMITTED IS 8.3'. THIS DOESN'T REFLECT POST |
| HEIGHT IN PLANS. REVISE AS REQUIRED TO COMPLY. SEC. |
| R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 7- SPECIFY SIZE OF EXISTING FOOTING. SEC. R301.1 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE ONLY THE DETAILS AND TABLES THAT APPLY TO |
| THIS PROJECT TO AVOID CONFLICTS OF CONFUSION. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. |
| |