2014-11-24 15:41:07ROUTED TO MISC. 2
  
 11/24/2014
 PROJECT: MARATHON SIGN
 PERMIT#: 14100682
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. THE INFORMATION AT THE TOP OF SHEET C2.0
 ABOVE THE MARATHON SIGN IS NOT LEGIBLE.
  
 2) NEC 600.3 AND 11O.3(B)
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. PROVIDE THE
 LISTING INFORMATION FOR THE SIGN AS A WHOLE AND FOR THE
 DRIVERS TO BE INSTALLED FOR OPERATION OF THE LED'S
  
 3) NEC 600.6(A)(1)
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR
 OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. INDICATE OM
 THE PLANS WHERE AND HOW THE PROPOSED INSTALLATION WILL
 CONFORM TO THE NEC 600.6
  
 4) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. INDICATE ON THE
 PLAN HOW THE COMPLETED INSTALLATION WILL COMPLY WITH
 THE FBC-E 505.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  