| PROJECT: MARATHON SIGN |
| PERMIT#: 14100680 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION |
| |
| 1) NEC 600.5 |
| EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. VERIFY ON SITE. |
| |
| 2) 600.3 LISTING. |
| ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| OTHERWISE APPROVED BY SPECIAL PERMISSION. VERIFY ON |
| SITE. |
| |
| 3) NEC 600.6(A)(1) LOCATION. |
| EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR |
| OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. |
| VERIFY ON SITE. |
| |
| 4) FBC-E 505.2.4 |
| ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| OF POWER FOR A MINIMUM OF 10 HOURS. VERIFY ON SITE. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |