| PROJECT: EDUCATIONAL GALLERY |
| PERMIT#: 14100679 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) NO ELECTRICAL PLANS INCLUDED IN SUBMITTAL. PROVIDE |
| ELECTRICAL PLANS INDICATING THE FOLLOWING: |
| A) WHAT IS EXISTING AND WHAT IS PROPOSED. |
| B) INDICATE ALL EMERGENCY EGRESS LIGHTING. |
| C) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| PANELS. |
| D) DETAIL ANY DEMOLITION OF EXISTING CIRCUITRY AND THE |
| INSTALLATION OF ANY NEW WORK. |
| |
| 2) EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. NEC 600.5 |
| |
| 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| TO FBC 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |