Plan Review Notes
Plan Review Notes For Permit 14100651
Permit Number 14100651
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-02-19 11:51:23PREVIOUS COMMENTS HAVE BEEN REPOSTED TO THIS PROJECT.
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 CONSIDER THESE AS PROVISO:
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 IF THE DOORS WILL BE EQUIPPED WITH A LOCK/LATCH,
 INDICATE HOW THE LOCK/LATCH WILL BE RELEASED FROM THE
 EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 THE MAIN ENTRY IS PERMITTED TO BE EQUIPPED WITH A KEYED
 LOCK WITH LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE
 STATING THE DOOR IS TO REMAIN UNLOCKED DURING BUSINESS
 HOURS. NO OTHER LOCKING OR LATCHING MECHANISMS ARE
 PERMITTED.
  
 THUMB-TURN LOCK IS TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.