Plan Review Notes
Plan Review Notes For Permit 14100630
Permit Number 14100630
Review Stop E
Sequence Number 3
Notes
Date Text
2015-06-10 16:42:186/10/2015
 PROJECT: LOFTIN PLACE
 PERMIT#: 14030096
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW OF REVISION# 14100630
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SHEET E-1.1.1
 RELOCATE NOTE THAT WAS ADDED REGARDING THE SITE AND
 LANDSCAPE LIGHTING IN THE VICINITY OF THE POOL. THE
 NOTE WAS INADVERTENTLY PLACED ON TOP OF THE PLAN AND IS
 DIFFICULT TO SPOT AND READ. RELOCATE THE NOTE FOR
 CLARIFICATION TO AN OPEN SPACE ON THE SHEET WHERE IT
 WILL BE EASIER TO SPOT AND READ. WPB AMENDMENTS TO FBC
 107.
  
 2) E-4.1
 A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS
 LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE
 LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND
 ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS.
 B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST
 COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES
 CLOSET.
 C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW
 VOLTAGE PANELS. NEC 110.26(D)
 D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING
 OUTLET. NEC 210.70
 THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN
 BUT NO SWITCH CONTROLLED LIGHT OUTLET.
  
 3) E-4.2
 A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS
 LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE
 LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND
 ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS.
 B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST
 COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES
 CLOSET.
 C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW
 VOLTAGE PANELS. NEC 110.26(D)
 D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING
 OUTLET. NEC 210.70
 THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN
 BUT NO SWITCH CONTROLLED LIGHT OUTLET.
  
 4) E-6.1.1
 SWITCHBOARD ?4?, CIRCUIT 3 FEEDS PANEL L FROM A 350AMP
 OCPD AND INDICATES TO REFERENCE THE PANEL SCHEDULE FOR
 PANEL ?L? FOR THE FEEDER SIZE. PANEL L DOES NOT
 INDICATE THE FEEDER SIZE, NEITHER DOES THE RISER
 DIAGRAM. THE RISER DIAGRAM INDICATES TO REFERENCE NOTE
 17 FOR THE FEEDER SIZE. BUT NOTE 17 SAYS TO REFERENCE
 THE PANEL SCHEDULE. PROVIDE THE FEEDER SIZE FOR THE
 FEEDER FROM SWITCHBOARD ?4? TO PANEL L
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING,
 GENERATORS, FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  