2015-06-10 16:42:18 | 6/10/2015 |
| PROJECT: LOFTIN PLACE |
| PERMIT#: 14030096 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW OF REVISION# 14100630 |
| ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| 1) SHEET E-1.1.1 |
| RELOCATE NOTE THAT WAS ADDED REGARDING THE SITE AND |
| LANDSCAPE LIGHTING IN THE VICINITY OF THE POOL. THE |
| NOTE WAS INADVERTENTLY PLACED ON TOP OF THE PLAN AND IS |
| DIFFICULT TO SPOT AND READ. RELOCATE THE NOTE FOR |
| CLARIFICATION TO AN OPEN SPACE ON THE SHEET WHERE IT |
| WILL BE EASIER TO SPOT AND READ. WPB AMENDMENTS TO FBC |
| 107. |
| |
| 2) E-4.1 |
| A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS |
| LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE |
| LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND |
| ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS. |
| B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST |
| COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES |
| CLOSET. |
| C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW |
| VOLTAGE PANELS. NEC 110.26(D) |
| D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING |
| OUTLET. NEC 210.70 |
| THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN |
| BUT NO SWITCH CONTROLLED LIGHT OUTLET. |
| |
| 3) E-4.2 |
| A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS |
| LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE |
| LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND |
| ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS. |
| B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST |
| COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES |
| CLOSET. |
| C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW |
| VOLTAGE PANELS. NEC 110.26(D) |
| D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING |
| OUTLET. NEC 210.70 |
| THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN |
| BUT NO SWITCH CONTROLLED LIGHT OUTLET. |
| |
| 4) E-6.1.1 |
| SWITCHBOARD ?4?, CIRCUIT 3 FEEDS PANEL L FROM A 350AMP |
| OCPD AND INDICATES TO REFERENCE THE PANEL SCHEDULE FOR |
| PANEL ?L? FOR THE FEEDER SIZE. PANEL L DOES NOT |
| INDICATE THE FEEDER SIZE, NEITHER DOES THE RISER |
| DIAGRAM. THE RISER DIAGRAM INDICATES TO REFERENCE NOTE |
| 17 FOR THE FEEDER SIZE. BUT NOTE 17 SAYS TO REFERENCE |
| THE PANEL SCHEDULE. PROVIDE THE FEEDER SIZE FOR THE |
| FEEDER FROM SWITCHBOARD ?4? TO PANEL L |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING, |
| GENERATORS, FIRE ALARM, ACCESS CONTROL SYSTEM, |
| SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, |
| COMMUNICATION. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |