2015-03-05 13:07:21 | 3/3/2015 |
| PROJECT: LOFTIN PLACE REVISION |
| PERMIT#: REVISION TRACKING# 14030096 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW OF REVISION 14100630 |
| ACTION: DENIED |
| |
| SHEET E-1.1.0 |
| ADD NOTES TO ADDRESS THE AUTOMATIC CONTROL OF INTERIOR |
| AND EXTERIOR LIGHTING AS REQUIRED THROUGHOUT. FBC |
| 505.2.2 |
| THIS NOTE SHOULD ALSO BE ADDED TO THE PANEL SCHEDULES |
| CONTROLLING LIGHTING IN THESE COMMON AREAS |
| |
| SHEET E-1.1.1 |
| 1) MOVE THE NEW NOTE THAT WAS INCLUDED TO ADDRESS THE |
| PREVIOUS REVIEW COMMENT REGARDING LIGHTING IN THE |
| VICINITY OF A SWIMMING POOL. NEC ARTICLE 680.8-10. THIS |
| NOTE WAS PLACED ON TOP OF THE PLAN RATHER THAN BEING |
| PLACED IN AN OPEN SPACE FOR CLARITY. |
| |
| SHEET E-2.1.1 |
| 2) MOVE THE NOTE ?ALL CORRIDOR RECEPTACLES SHALL BE |
| GFCI AND TAMPER RESISTANT? THIS NOTE WAS PLACED ON TOP |
| OF THE PLAN RATHER THAN BEING PLACED IN AN OPEN SPACE |
| FOR CLARITY. THE SYMBOL SHOULD BE CHANGED IN ALL |
| CORRIDORS TO INDICATE THIS PARTICULAR OUTLET TYPE ON |
| THE FLOOR PLAN. |
| |
| SHEET E-4.1 AND E-4.2 |
| 3) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING |
| OUTLET. NEC 210.70 |
| THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN |
| BUT NO SWITCH CONTROLLED LIGHT OUTLET. THE GREAT ROOM |
| INDICATES A SWITCH CONTROLLED RECEPTACLE BUT THE SYMBOL |
| FOR THE OUTLET IS NOT DESIGNATED AS A SWITCH CONTROLLED |
| RECEPTACLE. |
| |
| 4) THE OUTLETS REQUIRED BY 210.52 (SPACING) DO NOT |
| INCLUDE THE OUTLETS INDICATED FOR WALL MOUNTED TV?S |
| WHERE THE RECEPTACLE OUTLET WILL BE INSTALLED ABOVE OR |
| WHERE THEY ARE CONTROLLED BY A SWITCH SUCH AS IN THE |
| GREAT ROOM. 210.52 ADDITIONAL RECEPTACLE OUTLET ARE |
| REQUIRED TO MEET THIS CRITERIA. |
| |
| 5) ADDITIONAL OUTLETS ARE REQUIRED AT THE KITCHEN |
| COUNTERTOP BETWEEN THE STOVE AND THE SINK. 210.52 |
| |
| 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| PLANS AND ENGINEERING ARE REQUIRED FOR SITE LIGHTING, |
| GENERATORS. HOOD EXHAUST, FIRE ALARM, ACCESS CONTROL |
| SYSTEM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, |
| AND, COMMUNICATION. |
| |
| SHEET E-4.3 |
| 7) ADDITIONAL EMERGENCY LIGHTING IS REQUIRED FOR THE |
| COMMON AREA CORRIDORS, STAIRS, AND LOBBY AREAS. NEC |
| 700.16, 700.12 |
| |
| SHEET E-6.11 |
| 8) PARKING LOT LIGHTS ARE ALSO REQUIRED TO BE |
| CONTROLLED SO AS NOT TO BE IN OPERATION WHEN NOT |
| REQUIRED OR DURING DAYTIME HOURS. THE REQUIREMENTS OF |
| FBC-ENERGY SECTION 505.2 WILL ALSO APPLY TO THESE |
| CIRCUITS. |
| |
| SHEET E-6.1.2 |
| 9) A SIMPLE TIME CLOCK IS NOT SUFFICIENT FOR CONTROL OF |
| THE EXTERIOR LIGHTING TO COMPLY WITH THE FBC-ENERGY |
| SECTION 505.2. STATES: ?LIGHTING FOR ALL EXTERIOR |
| APPLICATIONS NOT EXEMPTED IN SECTION 505.1 SHALL HAVE |
| AUTOMATIC CONTROLS CAPABLE OF TURNING OFF EXTERIOR |
| LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN |
| THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME HOURS. |
| LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION |
| SHALL BE CONTROLLED BY EITHER A COMBINATION OF A |
| PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME |
| SWITCH.? |
| |
| SHEET E-9.1.1 |
| 10) REVISE THE LIGHTING FIXTURE SCHEDULE TO INCLUDE THE |
| FIXTURES STAIRWAY LIGHTING THAT ARE REQUIRED TO HAVE |
| BATTERY BACKUP. NONE OF THE SYMBOLS IN THE LEGEND |
| INCLUDE THE FIXTURE SYMBOL THAT HAS BEEN ADDED IN THE |
| STAIRWAYS THAT REQUIRE BATTERY BACKUP. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |