2015-02-28 13:14:22 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. SEE PROVISO ITEM FROM PERMIT ISSUANCE: |
| |
| (33). EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO |
| ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS |
| AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE |
| INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF |
| EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED; |
| PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS. THIS |
| SHEET IS NOT REQUIRED TO BE SUBMITTED AT THIS TIME. |
| |
| 2ND REVIEW, I APOLOGIZE FOR THE AMBIGUOUS LANGUAGE IN |
| PREVIOUS REVIEW. PROVISO 33 WAS FROM THE TIME OF PERMIT |
| ISSUANCE (AND COPIED AND PASTED INTO REVISION REVIEW). |
| PLAN WAS REDLINED AT THAT TIME WITH THE REQUEST THAT |
| THE LANGUAGE BE INCORPORATED INTO THE ARCHITECT?S PLAN |
| BUT NOT REQUIRED TO BE SUBMITTED AT THAT TIME (MEANING |
| THE TIME OF ISSUANCE OF THE PERMIT). |
| |
| THE LANGUAGE WAS NOT INCORPORATED INTO THE PLAN, AS |
| EVIDENCED BY THE REVISION SUBMITTED WITHOUT THE REVISED |
| LANGUAGE REGARDING GATES. SO THAT REQUREMENTS ARE CLEAR |
| TO ALL PARTIES (CONTRACTOR, SUBS, INSPECTORS), PLEASE |
| INCORPORATE THIS LANGUAGE INTO ARCHITECT'S PLAN AT THIS |
| TIME. |
| |
| 3. A0.1.2 AND OTHER SHEETS (LEVELS), EXIT ACCESS IS |
| INTERRUPTED BY THE PARKING GARAGE AREA, SEE FBC 1020.1; |
| LEVEL OF PROTECTION IS TO BE MAINTAINED UNTIL EXIT |
| DISCHARGE. OCCUPANT ENTERS THE RATED CORRIDOR FROM THE |
| UNIT, THEN ENTERS THE PARKING GARAGE OR OTHER NON RATED |
| STORAGE AREA (SEE MARK ON PLAN), THEN ENTERS THE RATED |
| EXIT STAIR. PLEASE REVISE TO PROVIDE CONTINUOUS |
| PROTECTION. |
| 2ND REVIEW, THIS PORTION OF THE PLAN WAS NOT REVISED. |
| SHEET A0.1.2 HAS BEEN MARKED TO NOTE LOCATION OF NON |
| CONTINUITY. |
| |
| 8. A0.1.5, 8TH LEVEL LIFE SAFETY PLAN, SOME ITEMS FROM |
| THE ROOF DECK BELOW ARE NOT GREYED OUT. FOR INSTANCE, A |
| DOOR IS SHOWN OPENING INTO WHAT APPEARS TO BE A |
| CONCRETE EYEBROW TO WHAT APPEARS TO BE OPEN SPACE, ROOF |
| DECK BELOW (AT STAIR 3). THIS DOOR IS NOT SHOWN ON |
| A2.1.8. PLEASE CORRELATE, GREY OUT ITEMS NOT ACTUALLY A |
| PART OF THE 8TH LEVEL, OR PROVIDE AREA/ROOM DESIGNATION |
| FOR CLARITY, FBC 107. |
| 2ND REVIEW, PURPOSE OF THE DOOR IS NOT CLEAR. IT |
| APPEARS TO OPEN ONTO A DROP TO THE LEVEL BELOW. ALSO |
| THERE IS ANOTHER AREA WHICH IS NOT CLEAR AS TO WHAT THE |
| RECTANGLES DEPICT. THESE TWO AREAS HAVE BEEN MARKED |
| (CLOUDED) ON THE PLAN. |
| |
| NEW COMMENTS: |
| |
| REV2 1: THIS IS A REMINDER THAT TEST REPORTS FOR |
| FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO |
| INSTALLATION. PLEASE BE ADVISED THAT, AT THIS TIME, NO |
| MANUFACTURER HAS PROVIDED ALL THREE TESTS (FLAME SPREAD |
| PER FBC 603.1/803.1.1, IIC PER FBC 1207.3, STC PER FBC |
| 1207.2) FOR TILE ON A 6" SLAB WITHOUT A DROPPED |
| CEILING. IF YOU DO NOT INTEND TO FIELD TEST FOR SOUND |
| (SO A STC/IIC OF 45 IS REQUIRED RATHER THAN 50) YOU ARE |
| ENCOURAGED TO ADDRESS THIS ISSUE TIMELY. PLEASE FEEL |
| FREE TO CONTACT ME TO DISCUSS WHEN YOU ARE READY TO |
| MAKE THE FLOORING UNDERLAYMENT SELECTION. |
| |
| REV2 2: LOUVERS ARE SHOWN ON SHEET A2.1.2 AND POSSIBLY |
| OTHER LOCATIONS, GLASS BLOCK SHOWN ON LEGEND ON A SHEET |
| ELEVATIONS (FOR EXAMPLE, A3.1.2). PRODUCT APPROVALS FOR |
| ALL COMPONENTS, CLADDING, LOUVERS ARE TO BE SUBMITTED |
| (AS A SUBMITTAL, NO FEE) FOR REVIEW PRIOR TO |
| INSTALLATION. REVIEW BY DESIGNER OF RECORD REQUIRED |
| PRIOR TO SUBMITTAL. IF SUBMITTED IN PAPER FORM, THREE |
| SETS REQUIRED. PLEASE NOTE THAT DIGITAL ONLY WILL BE |
| REQUIRED AT SOME POINT IN THE NEAR FUTURE. |
| |
| REV2 3: A2.1.6, A PORTION OF TWO APARTMENTS AND WHAT |
| APPEARS TO POSSIBLY BE STAIR #2 ARE SHOWN OUTSIDE OF |
| THE BUILDING ENVELOPE (NW CORNER OF BUILDING). THIS HAS |
| BEEN MARKED (CLOUDED) ON THE SHEET. PLEASE REMOVE OR |
| CLARIFY. |
| |
| REV2 4: SHEET S0.3 GENERAL NOTE M11 REFERS TO NOA |
| 14-0903.02 (CAST CRETE LINTELS). WHEN RESUBMITTING, |
| PLEASE UPLOAD THIS NOA FOR THE PERMIT RECORD. |
| |
| REV2 5: SHEET M2.1.3, CORRIDOR TO STORAGE (SE PORTION |
| OF BUILDING), PENETRATIONS THROUGH RATED WALLS REQUIRE |
| A FIRE DAMPER, FBC 709.9, 716. 4TH FLOOR ALSO MISSING |
| FD IN SAME LOCATION. CHECK ALL AND REVISE ACCORDINGLY. |
| |
| |
| |
| |