| WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 1) DWG. P-5.1 - THE WATER RISER FOR UNIT # B1 APPEARS |
| TO HAVE THE PIPE SIZES REVERSED AND THE HOT AND COLD |
| WATER LINES ARE REVERSED AT SOME OF THE FIXTURES. MOST |
| OF THE FIXTURES ARE BEING FED FROM A 1/2 " COLD WATER |
| LINE. |
| 2) DWG. P-5.4C - RISER #117 - THE VENT STACK IS SHOWN |
| AS 3" AND ON SHT. P-5.3 IT IS SHOWN AS 4". CLARIFY. |
| 3) SHT.P-5.4C - RISER #113 IS LABELED AS RISER #13 - |
| CORRECT |
| 4) DWG.P-5.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE |
| FIXTURE UNIT LOAD FOR THE WATER PIPING. |
| 5) WG. P-5.5 - STORM COLLECTION RISER #1 - A 3" ROOF |
| DRAIN WITH A COLLECTION AREA OF 1520 SQ. FT.IS |
| DISCHARGING INTO A HORIZONTAL LINE THAT IS 4 " IN |
| DIAMETER. THE MAXIMUM SQUARE FOOTAGE PERMITTED ON A 4" |
| LINE AT MIN. 1/8" SLOPE IS 1504 SQ. FT. THIS LINE HAS |
| TO BE INCREASED TO 5 " OR THE SLOPE OF THE PIPE SHALL |
| BE INCREASED TO 1/4 " SLOPE PER FT. |
| 6) PROVIDE A LEGEND FOR THE HOT AND COLD WATER LINES ( |
| THE WATER RISERS SHOW THE LINES IDENTIFIED WITH ONE AND |
| TWO DASHES. JUST IDENTIFY WHICH ONE IS FOR HOT AND |
| WHICH ONE IS FOR COLD). |
| 7) SHT. P-5.3 - THE BOTTOM HALF OF THE PAGE - THE |
| GROUPS OF RISER NUMBERS ARE SPACED SO CLOSE TO EACH |
| OTHER THAT IT IS DIFFICULT TO FIGURE OUT WHICH RISER |
| NUMBERS APPLY TO THE SPECIFIC RISERS. |
| 8) DWG. P-5.3 - SHOWS RISER # 117 FOR TWO DIFFERENT |
| RISERS - CLARIFY. |
| 9) DWG.P-6.2 - A WATER HAMMER ARRESTOR SHALL BE |
| INSTALLED ON THE TRASH CHUTE WASHDOWN PER 2010 FPC |
| SEC.604.9. |
| 10) DWG. P-6.2 - THE EJECTOR SHALL BE PROVIDED WITH A |
| FULL FLOW VALVE ( SHUTOFF VALVE) AND CHECK VALVE |
| LOCATED IN THE DISCHARGE PIPING BETWEEN THE PUMP OR |
| EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. 2010 FPC |
| SEC.712.2. |
| 11) IF THE ELEVATOR IS A HYDRAULIC ELEVATOR THE |
| EFFLUENT FROM THE SUMP PIT SHALL DISCHARGE INTO AN OIL |
| SEPARATOR. INDICATE ON THE DRAWING IF THE ELEVATOR IS |
| CBLE DRIVEN OR HYDRAULIC. |
| 12) DWG. P-6.2 - INDICATE ON THE PLAN WHETHER THE FLOOR |
| DRAIN RECEIVING THE WASTE FROM THE ELEVATOR PIT IS |
| DISCHARGING TO THE STORM OR SANITARY. |
| 13) DWG. P-5.4B - INDICATE THE SLOPE OF THE 8" SANITARY |
| LINE ON THE DRAWING. COMPLY W/2010 FPC TABLE 710.1 (1) |
| FOR THE SLOPE OF PIPE AND THE MAXIMUM NUMBER OF FIXTURE |
| UNITS THAT THE PIPE CAN CARRY. |
| 14) ANY WASHING MACHINE BOXES LOCATED IN FIRE RATED |
| WALLS SHALL EITHER BE FIRE RATED OR INSTALLED TO |
| MAINTAIN THE FIRE RATING OF THE WALL. 2010 FBC SEC.713. |
| 15) DWG. P-6.2 - THE P & T LINES AND PAN DRAINS SHALL |
| NOT USE THE SAME RISER PER THE 2010 FPC SEC.504.6 (4). |
| 16) DWG.P-6.2 - THE PAN DRAIN SHALL BE DRAINED BY AN |
| INDIRECT WASTE PIPE PER THE 2010 FPC SEC. 504.7.1. |
| 17) DWG. P-5.6A - SHOWS THE RELIEF LINES AS A DIRECT |
| CONNECTION TO THE RISER AND THE WATER HEATER DETAIL ON |
| DWG. P-6.2 SHOWS RELIEF LINES DISCHARGING TO AN AIR GAP |
| FITTING . CLARIFY. |
| 18) COMBUSTIBLE MATERIALS ARE NOT PERMITTED IN RETURN |
| AIR PLENUMS PER THE 2010 FPC SEC.307.6 FL. MECH CODE. |
| SEC.602.2.1. |
| |