Plan Review Notes
Plan Review Notes For Permit 14100630
Permit Number 14100630
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-07 07:36:08 
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) DWG. P-5.1 - THE WATER RISER FOR UNIT # B1 APPEARS
 TO HAVE THE PIPE SIZES REVERSED AND THE HOT AND COLD
 WATER LINES ARE REVERSED AT SOME OF THE FIXTURES. MOST
 OF THE FIXTURES ARE BEING FED FROM A 1/2 " COLD WATER
 LINE.
 2) DWG. P-5.4C - RISER #117 - THE VENT STACK IS SHOWN
 AS 3" AND ON SHT. P-5.3 IT IS SHOWN AS 4". CLARIFY.
 3) SHT.P-5.4C - RISER #113 IS LABELED AS RISER #13 -
 CORRECT
 4) DWG.P-5.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 FIXTURE UNIT LOAD FOR THE WATER PIPING.
 5) WG. P-5.5 - STORM COLLECTION RISER #1 - A 3" ROOF
 DRAIN WITH A COLLECTION AREA OF 1520 SQ. FT.IS
 DISCHARGING INTO A HORIZONTAL LINE THAT IS 4 " IN
 DIAMETER. THE MAXIMUM SQUARE FOOTAGE PERMITTED ON A 4"
 LINE AT MIN. 1/8" SLOPE IS 1504 SQ. FT. THIS LINE HAS
 TO BE INCREASED TO 5 " OR THE SLOPE OF THE PIPE SHALL
 BE INCREASED TO 1/4 " SLOPE PER FT.
 6) PROVIDE A LEGEND FOR THE HOT AND COLD WATER LINES (
 THE WATER RISERS SHOW THE LINES IDENTIFIED WITH ONE AND
 TWO DASHES. JUST IDENTIFY WHICH ONE IS FOR HOT AND
 WHICH ONE IS FOR COLD).
 7) SHT. P-5.3 - THE BOTTOM HALF OF THE PAGE - THE
 GROUPS OF RISER NUMBERS ARE SPACED SO CLOSE TO EACH
 OTHER THAT IT IS DIFFICULT TO FIGURE OUT WHICH RISER
 NUMBERS APPLY TO THE SPECIFIC RISERS.
 8) DWG. P-5.3 - SHOWS RISER # 117 FOR TWO DIFFERENT
 RISERS - CLARIFY.
 9) DWG.P-6.2 - A WATER HAMMER ARRESTOR SHALL BE
 INSTALLED ON THE TRASH CHUTE WASHDOWN PER 2010 FPC
 SEC.604.9.
 10) DWG. P-6.2 - THE EJECTOR SHALL BE PROVIDED WITH A
 FULL FLOW VALVE ( SHUTOFF VALVE) AND CHECK VALVE
 LOCATED IN THE DISCHARGE PIPING BETWEEN THE PUMP OR
 EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. 2010 FPC
 SEC.712.2.
 11) IF THE ELEVATOR IS A HYDRAULIC ELEVATOR THE
 EFFLUENT FROM THE SUMP PIT SHALL DISCHARGE INTO AN OIL
 SEPARATOR. INDICATE ON THE DRAWING IF THE ELEVATOR IS
 CBLE DRIVEN OR HYDRAULIC.
 12) DWG. P-6.2 - INDICATE ON THE PLAN WHETHER THE FLOOR
 DRAIN RECEIVING THE WASTE FROM THE ELEVATOR PIT IS
 DISCHARGING TO THE STORM OR SANITARY.
 13) DWG. P-5.4B - INDICATE THE SLOPE OF THE 8" SANITARY
 LINE ON THE DRAWING. COMPLY W/2010 FPC TABLE 710.1 (1)
 FOR THE SLOPE OF PIPE AND THE MAXIMUM NUMBER OF FIXTURE
 UNITS THAT THE PIPE CAN CARRY.
 14) ANY WASHING MACHINE BOXES LOCATED IN FIRE RATED
 WALLS SHALL EITHER BE FIRE RATED OR INSTALLED TO
 MAINTAIN THE FIRE RATING OF THE WALL. 2010 FBC SEC.713.
 15) DWG. P-6.2 - THE P & T LINES AND PAN DRAINS SHALL
 NOT USE THE SAME RISER PER THE 2010 FPC SEC.504.6 (4).
 16) DWG.P-6.2 - THE PAN DRAIN SHALL BE DRAINED BY AN
 INDIRECT WASTE PIPE PER THE 2010 FPC SEC. 504.7.1.
 17) DWG. P-5.6A - SHOWS THE RELIEF LINES AS A DIRECT
 CONNECTION TO THE RISER AND THE WATER HEATER DETAIL ON
 DWG. P-6.2 SHOWS RELIEF LINES DISCHARGING TO AN AIR GAP
 FITTING . CLARIFY.
 18) COMBUSTIBLE MATERIALS ARE NOT PERMITTED IN RETURN
 AIR PLENUMS PER THE 2010 FPC SEC.307.6 FL. MECH CODE.
 SEC.602.2.1.
  