Plan Review Notes
Plan Review Notes For Permit 14100630
Permit Number 14100630
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-12 09:33:0512/11/2014
 PROJECT: LOFTIN PLACE REVISION
 PERMIT#: 14030096
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW OF REVISION 14100630
 ACTION: DENIED
  
 SHEET E-1.1.1
 1) VERIFY THE LOCATION, AND ELEVATION OF POWER AND
 LIGHTING INCLUDING THEIR ASSOCIATED CONDUITS AND WIRING
 IN THE VICINITY OF THE SWIMMING POOL. NEC680.8.680.10,
 680.22, 680.24
  
 SHEET E-2.1.2
 1) EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT
 OF SAME LOCAL AREA. NEC 700.12 (F) (4)
  
 E.2.1.7
 2) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED
 IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE
 OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT
 DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT
 REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. FBC
 505.2.4 EXTERIOR LIGHTING CONTROLS.
  
 3) PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES
 INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609
  
 SHEET E-4.1
 4) STUDIO ONE UNIT REQUIRES AN OUTLET AT THE KITCHEN
 ISLAND. NEC 210.52
  
 SHEET 4.1A
 5) PANEL A1 INDICATES CIRCUIT #1,3 FOR THE A/C IS A
 2POLE 35 WITH #12. REVISE THE PANEL SCHEDULE TO
 INDICATE A CIRCUIT CONDUCTOR ADAQUATE FOR THE 35AMP
 OCPD. NEC 310.16
  
 E-4.3
 6) THE CORRIDORS AND COMMON AREAS REQUIRE EMERGENCY
 LIGHTING. LIGHTING SYSTEMS SHALL BE DESIGNED AND
 INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL
 LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP,
 CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES
 EMERGENCY ILLUMINATION. NEC 700.16
  
 7) IDENTIFY ALL LIGHTING CIRCUITS ON THE FLOOR PLAN.
 FBC 107.3.2
  
 8) EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT
 OF SAME LOCAL AREA. NEC 700.12 (F) (4)
  
 E-4.4
 9) PROVIDE EMERGENCY LIGHTING FOR STAIRWELLS. EMERGENCY
 LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO
 THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT,
 SUCH AS THE BURNING OUT OF A LAMP, CANNOT LEAVE IN
 TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY
 ILLUMINATION. NEC 700.16
  
 E-5.1.1
 10) CLARIFY THE CIRCUIT FEEDING THE FIRE PUMP. THE
 RISER ON 7.1.1 INDICATES THE FIRE PUMP SERVICE FROM THE
 UTILITY TO THE FIRE PUMP CONTROLLER AND THE FLOOR PLAN
 ON SHEET 5.1.1 INDICATES THE FIRE PUMP BEING FED FROM
 SWITCHBOARD 4 CIRCUIT #10 AND THE PANEL SCHEDULE FOR
 SWITCH BOARD 4 CIRCUIT #10 INDICATES A SPACE. REVISE
 THE FLOOR PLAN ON SHEET 5.1.1 TO INDICATE THE ACTUAL
 FEEDER.
  
 E-6.1.1
 11) REVISE PANEL SCHEDULES AND LOAD CALCULATIONS IN
 SWITCH BOARD 2 AND 3. THE TOTAL CALCULATED LOADS
 REPRESENTED IN THE CHART LABELED TOTAL UNIT CONNECTED
 LOAD STATES THE TOTAL CONNECTED LOAD IN VA PER METER
 CENTER. THE PANEL SCHEDULE FOR SWITCH BOARD ?3?
 INDICATES THE LOADS TO BE SLIGHTLY DIFFERENT THAN WHAT
 IS REPRESENTED IN THE CHART ON E7.1.1 PARTICULARLY THE
 LOAD FOR METER CENTER 8. THE PANEL SCHEDULE ON E6.1.1
 INDICATES MC 8 WITH A TCL OF 847.7KVA BUT THE LOAD
 INDICATED IN THE CHART ON E7.1.1 IS INDICATED TO BE
 1,078,144VA OR 1,078KVA. REVISE LOADS IN PANEL
 SCHEDULES AND LOAD CALCULATIONS TO BE ACCURATE AND TO
 MATCH FROM PAGE TO PAGE
  
 E-7.1.1. AND E-7.1.2
 12) NEC240.4(C) WHERE THE OVERCURRENT DEVICE IS RATED
 OVER 800 AMPERES, THE AMPACITY OF THE CONDUCTORS IT
 PROTECTS SHALL BE EQUAL TO OR GREATER THAN THE RATING
 OF THE OVERCURRENT DEVICE DEFINED IN NEC 240.6. 3 SETS
 OF 500MCM CU IS NOT ADEQUATE FOR A 1200AMP OCPD
 13) VERIFY SAME FOR ALL SERVICE ENTRANCE AND FEEDERS
  
 14) NEC240.4(C) DEVICES RATED OVER 800 AMPERES. WHERE
 THE OVERCURRENT DEVICE IS RATED OVER 800 AMPERES, THE
 AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE EQUAL
 TO OR GREATER THAN THE RATING OF THE OVERCURRENT DEVICE
 DEFINED IN NEC 240.6
 3 SETS OF 500MCM CU IS NOT ADEQUATE FOR A 1200AMP OCPD
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  