2014-12-08 18:33:16 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. SEE PROVISO ITEMS 17 AND 33 FROM BUILDING PLAN |
| REVIEW 3 FOR PERMIT 14030096 AND ADDRESS AT THIS TIME |
| OR ADVISE AS TO WHEN THEY WILL BE ADDRESSED. FOR YOUR |
| CONVENIENCE, THEY ARE AS FOLLOWS: |
| |
| (17). S1.8, ROOF DESIGN PRESSURES TREAT ZONE 3 AS ZONE |
| 2. PLEASE SEE ASCE7010, FIGURE 30.6-1, FOOTNOTE , |
| PARAPET TO BE EQUAL TO OR HIGHER THAN 3FT. DETAIL A |
| A7.1 APPEARS TO SHOW A 2FT PARAPET AT STAIR 1, PLEASE |
| CLARIFY OR INCLUDE ZONE 3 PRESSURES FOR ROOF CORNER |
| ZONES LACKING A 3 FT PARAPET. REVISE ROOF PLAN TO |
| CLARIFY WHERE HIGHER ZONE 3 DESIGN PRESSURES ARE |
| REQUIRED. PRIOR TO ROOF PERMIT APPLICATION, THIS SHEET |
| SHOULD EITHER BE REVISED OR REVISE DETAILS WHICH SHOW A |
| 2 FT HIGH PARAPET. THIS IS TO BE SUBMITTED AS A |
| REVISION PRIOR TO ROOF PERMIT APPLICATION. |
| (33). EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO |
| ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS |
| AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE |
| INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF |
| EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED; |
| PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS. THIS |
| SHEET IS NOT REQUIRED TO BE SUBMITTED AT THIS TIME. |
| |
| 2. STAIR 6 EXIT DISCHARGE, SHOW PATH TO PUBLIC WAY FBC |
| 1027.6. AREA BETWEEN END OF LANDING SHOWN AND SIDEWALK |
| IS NOT CLEAR. THE WALKWAY FROM STAIR 6 EXIT DISCHARGE |
| TO PUBLIC SIDEWALK IS STILL SHOWN ON SP1 (AND OTHER |
| SHEETS SUCH AS CIVILS) BUT THERE IS NO LONGER A DOOR IN |
| THIS LOCATION. THE NEW EXIT DOOR LOCATION DOES NOT |
| APPEAR TO INCLUDE AN EXIT DISCHARGE WHICH IS CONTINUOUS |
| TO THE PUBLIC WAY. |
| |
| 3. A0.1.2 AND OTHER SHEETS (LEVELS), EXIT ACCESS IS |
| INTERRUPTED BY THE PARKING GARAGE AREA, SEE FBC 1020.1; |
| LEVEL OF PROTECTION IS TO BE MAINTAINED UNTIL EXIT |
| DISCHARGE AFTER THE OCCUPANT ENTERS THE EXIT. IT |
| APPEARS THAT THE OCCUPANT ENTERS THE RATED CORRIDOR, |
| THEN ENTERS THE PARKING GARAGE OR OTHER NON RATED |
| STORAGE AREA, THEN ENTERS THE ENCLOSED STAIR. PLEASE |
| REVISE TO PROVIDE CONTINUOUS PROTECTION. |
| |
| 4. A0.1.2, A2.1.2, THE ACCESS AISLE FOR NORTH END |
| ACCESSIBLE PARKING SPACE HAS BEEN REMOVED, FBC 2010 |
| ACCESSIBILITY 502.3. CHECK ALL SHEETS. |
| |
| 5. A0.1.2, THE UNIT TYPES, OTHER ROOM DESIGNATIONS HAVE |
| BEEN REMOVED, PLEASE RESTORE (TO EXPEDITE PLAN REVIEW) |
| OR EXPLAIN RATIONALE FOR REMOVAL, FBC 107. |
| |
| 6. A0.1.2, THE FIRE RATED WALL BETWEEN UNITS AT THE |
| OPEN PORCH HAVE BEEN REMOVED. SPECIFY WALL TYPE. FOR |
| INSTANCE, SHEET A0.1.2, TWO CENTER UNITS AT NORTH |
| (PREVIOUSLY MARKED AS TWO A1 UNITS), OTHER LOCATIONS |
| ALSO AFFECTED. |
| |
| 7. A0.1.4, SOUTH WEST DOOR FROM DECK TO CORRIDOR SHOULD |
| SWING IN THE DIRECTION OF EGRESS TRAVEL FBC 1008.1.2. |
| |
| 8.A0.1.5, 8TH LEVEL LIFE SAFETY PLAN, SOME ITEMS FROM |
| THE ROOF DECK BELOW ARE NOT GREYED OUT. FOR INSTANCE, A |
| DOOR IS SHOWN OPENING INTO WHAT APPEARS TO BE A |
| CONCRETE EYEBROW TO WHAT APPEARS TO BE OPEN SPACE, ROOF |
| DECK BELOW (AT STAIR 3). THIS DOOR IS NOT SHOWN ON |
| A2.1.8. PLEASE CORRELATE, GREY OUT ITEMS NOT ACTUALLY A |
| PART OF THE 8TH LEVEL, OR PROVIDE AREA/ROOM DESIGNATION |
| FOR CLARITY, FBC 107. |
| |
| 9. A0.1.5, THE GRAPHICS FOR THE 2 HR RATED MECH SHAFTS |
| LOCATED IN THE SOUTH CORRIDOR, STAIR 2, ELEVATOR 1, ALL |
| OTHER 2 HOUR RATINGS HAVE BEEN REMOVED; PLEASE RESTORE |
| SO DESIGN INTENT IS CLEAR, FBC 708.4, 1022. |
| |
| 10. A2.1.1, IT APPEARS THAT PARKING SPACES WERE RE |
| NUMBERED SO THE DEDICATED LEASING PARKING SPACES NO |
| LONGER INCLUDE WHAT IS NOW ACCESSIBLE SPACE NUMBER 13 |
| (PREVIOUSLY SPACE NUMBER 11) AND THEREFORE DOES NOT |
| COMPLY WITH FBC 2010 ACCESSIBILITY 208.2. PLEASE |
| REVISE. COMPLIANCE WITH FAIR HOUSING AND ACCESSIBILITY |
| SHOULD BE CLEAR ON THE PLANS. |
| |
| INDEX PAGE INDICATES THAT SHEET SD 1 INCLUDES PARKING |
| DATA. I WAS UNABLE TO LOCATE SUMMARIZED PARKING ON THAT |
| SHEET OR ON ANY OTHER SHEET, PLEASE REVISE. |
| |
| 11. SHEET SP1 HAS A NOTE WHICH PREVIOUSLY STATED *481 |
| SPACES* AND NOW STATES *409 SPACES* BUT THIS NUMBER |
| DOES NOT APPEAR TO BE CONSISTENT WITH THE TOTAL OF THE |
| NUMBER OF PARKING SPACES FOR EACH FLOOR. CLARIFY TOTAL |
| UNIT SPACES, TOTAL SPACES DEDICATED TO LEASING AREA, |
| TOTAL ACCESSIBLE SPACES (SERVING THE LEASING AREA), |
| TOTAL ACCESSIBLE SPACES SERVING UNIT RESIDENTS AND |
| THEIR GUESTS. FBC 2010 ACCESSIBILITY/FAIR HOUSING. |
| |
| 12. SEE FIRE COMMENTS REGARDING DAMPERS AND EXIT |
| LIGHTING. THIS IS ALSO REQUIRED BY FBC 713 AND FBC |
| 1011.1. |
| |
| 13. S0.4, STRUCTURAL STEEL NOTE APPEARS INCOMPLETE, SEE |
| SS12. |
| |
| 14. SHEET S 1.4 HAS NOT BEEN CORRECTLY NAMED; THIS |
| SHOULD BE S1.4.4. SHEET S 1.4 HAS BEEN REMOVED FROM |
| THIS PROJECT (SEE INDEX SHEET) AND THE NEW SHEET S1.4.4 |
| SHOULD BE NAMED PROPERLY IN ORDER TO REPLACE THE |
| PREVIOUS VERSION. |
| |
| 15. DUE TO FILE NAMING, SOME SHEETS ARE NOT IN ORDER. |
| FOR INSTANCE, S1.3B APPEARS BEFORE S1.3A; SHEETS S1.4.4 |
| A THROUGH C DO NOT FOLLOW S1.4.4 (SO, THE STRUCTURAL |
| DRAWINGS FOR THE 4TH FLOOR FOLLOW THE 6TH FLOOR). |
| PLEASE COORDINATE WITH OUR PROJECTDOX COORDINATOR TO |
| DETERMINE THE IMPACT ON RECORDS RETENTION AND ISSUANCE |
| OF THE REVISION (IF ANY) OTHER THAN THE FACT THAT, IN |
| THE FIELD (FOR COORDINATION, CONSTRUCTION, AND |
| INSPECTIONS), PAGES WILL NOT BE IN THE ORDER ON THE |
| INDEX SHEET, AND STRUCTURAL INFORMATION BY FLOOR MAY |
| ALSO BE OUT OF ORDER. IT IS STRONGLY SUGGESTED THAT, |
| SINCE THE PLANS INCLUDE OVER 200 SHEETS, FILES BE |
| RENAMED SO THAT ALL SHEETS PRINT IN THE ORDER OF THE |
| INDEX PAGE, FBC 107. |
| |
| 16. SHEET S1.4.4B NOTE IN THE BOX NEAR THE BOTTOM RIGHT |
| CORNER REFERS TO SHEET S1.4A WHICH, ACCORDING TO THE |
| INDEX, NO LONGER EXISTS. PLEASE REVISE THIS AND ANY |
| OTHER NOTES WHICH REFER TO THE SHEETS (S1.4, 1.4A, |
| 1.4B, 1.4C) WHICH HAVE BEEN ELIMINATED. OR, RESTORE |
| SHEETS AND REVISE INDEX TO REFLECT, FBC 107. |
| |
| 17. GARAGE FRAMING NOTES APPEAR INCOMPLETE. SEE SHEET |
| S1.5A, *GARAGE FRAMING NOTES*, NOTES 4, 6 AND REVISE TO |
| REFER TO CORRECT SHEETS. PLEASE CHECK ALL SIMILAR NOTES |
| ON ALL SHEETS AS THIS APPEARS TO OCCUR ON OTHER SHEETS. |
| |
| 18. SEE ITEM 1 REGARDING PROVISO ITEM CONCERNING |
| PREVIOUS COMMENT LIST NUMBER 17. DETAIL 1 S1.7B DOES |
| NOT APPEAR TO SHOW A PARAPET AT THE ELEVATOR ROOF, AND |
| SHEET S1.7A (AND OTHER SHEETS, DETAILS) PARAPET LEGEND |
| SHOWS A 2FT PARAPET AT STAIRS. THIS COMMENT WAS IN |
| BUILDING PLAN REVIEWS 1 AND 2 AND PERMIT WAS ISSUED |
| WITH PROVISO THAT THIS BE REVISED. IF ENGINEER |
| DISAGREES WITH THIS COMMENT, PLEASE CONTACT ME. IF |
| ENGINEER DOES NOT DISAGREE WITH THIS COMMENT, PLEASE |
| EITHER REVISE ROOF PRESSURES ON SHEET S1.8 OR ADVISE AS |
| TO WHEN THIS SHEET WILL BE REVISED. |
| |
| PERMIT WAS ISSUED WITH PROVISO THAT THIS SHEET BE |
| REVISED (OR THIS ISSUE OTHERWISE RESOLVED) PRIOR TO |
| ISSUANCE OF THE ROOFING PERMIT. A ROOF SUB PERMIT WAS |
| APPLIED FOR ON NOV 25. A PRINT HOLD HAS BEEN PLACED ON |
| THIS PERMIT SUBJECT TO RESOLUTION OF THIS COMMENT. |
| |
| 19. S5.1, TYPICAL CONCRETE COLUMN, INCLUDES REFERENCE |
| TO PILE CAP. PLEASE REMOVE, FBC 107, OR INDICATE WHERE |
| PILES WILL BE INSTALLED. |
| |
| |