Plan Review Notes
Plan Review Notes For Permit 14100605
Permit Number 14100605
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-21 14:36:551. REMOVE FUTURE FROM PLAN. ONLY SUBMIT PLAN THAT SHOWS
 WORK THAT IS TO BE INSTALLED UNDER THIS PERMIT.
 2. FBC 107.3.5.3. PROVIDE COMPLETE SERVICE RISER
 DETAIL. SHOW FEEDER CONDUCTORS FROM 400 AMPERE
 DISCONNECT TO "MDP" PANEL.
 3. REMOVE ATS AND ASSOCIATED AND GENERATOR.