Plan Review Notes
Plan Review Notes For Permit 14100604
Permit Number 14100604
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-06 10:38:30TO S. HILL'S DESK FOR REVIEW OF WIND LOAD CALCULATIONS.
  
  
2014-11-06 09:41:2811/6/2014
 PROJECT: WPB 7TH ST SQUARE
 PERMIT#: 14100604
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE "ONE LINE DIAGRAM" AND CLARIFY DISCREPANCY
 BETWEEN "ONE LINE DIAGRAM" AND THE "PROPOSED SERVICE"
 DETAIL ON SHEET 2OF4. THE "ONE LINE DIAGRAM" INDICATES
 A SINGLE CIRCUIT 240V BUT DOES NOT INDICATE THE USE OF
 A SERVICE ENTRANCE RATED MAIN OCPD OR HOW THE
 "NIGHTMASTER LIGHTING CONTACTOR" IS FED. CO-ORDINATE
 BETWEEN THE TWO DIAGRAMS FOR COHESIVENESS. WPB
 AMENDMENTS TO THE FBC 107.2.1
  
 2) PROVIDE A PANEL SCHEDULE WITH SIZE OF OCPD FOR
 BRANCH CIRCUITS FEEDING LIGHT POLES AND BRANCH CIRCUIT
 FEEDING IRRIGATION CONTROLLER. WPB AMENDMENTS TO THE
 FBC 107.3.5, NEC 215
  
 3) INDICATE THE LOCATION OF THE FPL ELECTRICAL SERVICE.
 WPB AMENDMENTS TO THE FBC 107.2.1
  
 4) PROVIDE ADDITIONAL DETAILS FOR IRRIGATION
 CONTROLLER. IS IT HARD WIRED? OR PLUG IN? EITHER WAY,
 INDICATE THE MEANS OF DISCONNECT, LOAD AND VOLTAGE OF
 CIRCUIT. WPB AMENDMENTS TO THE FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  