Plan Review Notes
Plan Review Notes For Permit 14100604
Permit Number 14100604
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-08 14:02:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FAC 61G15-30 AND FAC61G15-18.001 AND OTHER
 PLACES. ENGINEER OF RECORD NOT CLEAR. ENGINEER OF
 RECORD IS TO REVIEW DELEGATED ENGINEERING AND SHOP
 DRAWINGS. THIS MAY BE DONE EITHER WITH A SHOP DRAWING
 REVIEW STAMP OR A LETTER.
  
 2. SHEET 1 OF 4 SHOWS LOCATION OF PROPOSED LIGHT POLES.
 IT APPEARS THAT THERE ARE THREE DIFFERENT TYPES OF
 POLES PROPOSED. PLANS DESCRIBE LOCATION OF POLES WITH
 BANNER ARM, ANOTHER NOTE INDICATES THAT THE POLE WITH
 BASE IS TO BE INSTALLED IN "RAIN GARDEN ONLY" BUT SITE
 PLAN DOES NOT SPECIFY LOCATION OF "RAIN GARDEN".
  
 REVISE PLAN TO INDICATE LOCATION OF PROPOSED POLE
 TYPES. EOR IS TO REVIEW SPECIFICATIONS & ENGINEERING
 FOR PROPOSED POLES (SEE COMMENT #1).
  
 3. SHEET 1 SHOWS LOCATION OF POLES WITH BANNER ARMS.
 THE MANUFACTURER RECOMMENDS AGAINST THE INSTALLATION OF
 BANNER ARMS AT 4'10" ABOVE GRADE. ENGINEER IS TO
 ACKNOWLEDGE STATEMENT AND PROVIDE RATIONALE FOR
 INSTALLATION. IS THIS DUE TO PEDESTRIAN OR VEHICULAR
 HAZARD, OR BECAUSE THE BANNER IS TO BE REMOVED AT WINDS
 EXCEEDING 70MPH?
  
 IF THIS IS DUE TO POTENTIAL HAZARD TO PEDESTRIANS AND
 THIS IS NOT NEAR A PEDESTRIAN PATH, IT IS RECOMMENDED
 THAT THE PLAN BE CLARIFIED TO INDICATE THAT THE
 POTENTIAL HAZARD HAS BEEN ADDRESSED. BASED ON THE
 LOCATION SHOWN ON THE PLAN, IT APPEARS THAT THE
 PROPOSED LOCATION MAY PRESENT A HAZARD TO VEHICLES.
  
 IF THIS BANNER IS TO BE REMOVED AT WINDS EXCEEDING
 70MPH AS STATED ON CALCS, PLAN PREPARED BY ENGINEER OF
 RECORD SHOULD REFLECT THIS IN HIS DESIGN CRITERIA. WHO
 IS TO BE RESPONSIBLE FOR THIS REMOVAL? IS THIS ALSO IN
 AASHTO LTS-6, OR AN EXCEPTION ELSEWHERE IN THE FBC?
 WILL THE ARM OF THE BANNER FAIL IF THE BANNER IS NOT
 REMOVED? HOW DOES FAILURE OF THE BANNER AFFECT THE
 LIGHT POLE?
  
 4. IF THE REMOVABLE BANNER IS NOT INCLUDED IN AASHTO
 LTS-6 OR AS AN EXCEPTION IN FBC 2010, THIS WOULD NEED
 TO BE CONSIDERED UNDER ALTERNATIVE MATERIALS AND
 METHODS FBC 104.11. THIS INSTALLATION WOULD MOST LIKELY
 BE HANDLED LIKE AN AWNING. THIS REQUIRES A REMOVAL
 LETTER BY THE OWNER ACKNOWLEDGING RESPONSIBILITY AND
 LABELING AS WELL AS REMOVAL INSTRUCTIONS. UNLESS
 COVERED UNDER AN FBC OR AASHTO, THIS WOULD REQUIRE
 BUILDING OFFICIAL APPROVAL.
  
 5. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC
 2010 1603.1.4. WIND SPEED IS INCLUDED ON CALCS BUT I
 WAS UNABLE TO LOCATE EXPOSURE CLASSIFICATION ON THE
 PLAN OR IN THE CALCS. PLEASE ADDRESS.
  
 6. BANNER ARMS ARE NOT SHOWN ON THE ENGINEER'S PLANS
 OTHER THAN THE NOTE ON SHEET 1. FBC 107, INCLUDE
 DIMENSIONS, SPECIFICATIONS. SEE ALSO ITEM 3.
  
 7. THERE ARE NOTES IN THE CALCS WHICH STATE THAT 140MPH
 (VASD) = 170MPH (VULT). THIS IS ACKNOWLEDGED. WHAT IS
 NOT IMMEDIATELY APPARENT IS WHETHER OR NOT 140MPH
 EXPOSURE ??? WITH A .77 IMPORTANCE FACTOR IS MORE
 CONSERVATIVE THAN 150MPH (VULT) EXPOSURE C. PLANS STATE
 THAT A .77 IMPORTANCE FACTOR WAS USED, BUT ISN'T THIS
 USED IN THE ASD, BUT BUILT INTO THE MAP FOR STRENGTH
 DESIGN, SO 150MPH IS USED, NOT 170MPH? DESIGN CRITERIA
 NOT CLEAR.
  
 AS I AM NOT AN ENGINEER, PLEASE FEEL FREE TO CONTACT ME
 TO DISCUSS AND EXPLAIN THE USE OF .77 IMPORTANCE FACTOR
 IN AASHTO LTS-6 (ASCE7-05??) AND SEPARATE WIND MAPS FOR
 RISK CATEGORIES AND THE EFFECT ON CALCULATIONS. AS I
 DON'T HAVE A COPY OF AASHTO LTS-6 (AND, IF WE ORDER A
 COPY OF AASHTO WILL MOST LIKELY ORDER THE VERSION
 REFERENCED IN THE FBC), I AM UNABLE TO COMPARE THE
 CALCULATIONS.
  
 8. FBC 1609.1.1 EXCEPTION 7, AASHTO LTS-4 IS LISTED AS
 AN EXCEPTION; CALCS WERE SUBMITTED USING AASHTO LTS-6.
 THIS IS CONSIDERED UNDER ALTERNATIVE MATERIALS AND
 METHODS FBC 104.11. PLEASE HAVE ENGINEER SUBMIT A
 LETTER FOR CONSIDERATION.
  
 9. REVISE SITE PLAN TO CLARIFY LOCATION AND RELATION TO
 PRIVATE PROPERTY LINES, FBC 1609. IT APPEARS TO BE
 LOCATED IN THE PUBLIC RIGHT OF WAY BUT NO PROPERTY
 LINES ARE SHOWN ON THE SITE PLAN.
  
 10. SEE FAC61G15-23, CALCULATIONS TO BE IN A FORMAT
 ACCEPTABLE TO FBPE. EITHER EACH SHEET IS TO INCLUDE A
 TITLE BLOCK AND BE SIGNED, SEALED, AND DATED OR AN
 INDEX SHEET USED WHICH INDENTIFIES EACH SHEET. SOME
 CALCULATIONS HAVE NEITHER A TITLE BLOCK NOR
 SIGNED/SEALED; NOT CLEAR WHO IS TAKING RESPONSIBILITY
 FOR THOSE CALCULATIONS. OTHER SHEETS ARE SIGNED AND
 SEALED ON COVER SHEET ONLY BUT LACK THE INDEX SHEET.
  
 FOR INSTANCE, "STRUCTURAL ANALYSIS FOR ROUND FLUTED
 PRESTRESSED CONCRET LUMINAIRE ELECTROLILER", 9 PAGES -
 NO TITLE BLOCK, NO INDEX, NOT SIGNED, SEALED & DATED.
 THIS FOLLOWS SHEET 1A OF 10 FOR A LIGHT POLE. THE SHEET
 FOR THE LIGHT POLE HAS A CATALOG NUMBER AND APPEARS TO
 BE ONE OF THE THREE AMERON POLES PROPOSED, BUT NOTHING
 ON THE SHEET TIES THIS DRAWING BACK TO THE THREE
 DIFFERENT LIGHT POLES PROPOSED WHICH ARE NAMED ON THE
 MANUFACTURER'S LETTER (AMERON DRAWING 1408-003, ETC.).
 IF THIS IS 1A OF 10, WHERE ARE THE OTHER SHEETS? DOES
 THE SHEET FROM THE ENGINEER COVER THIS SHEET? WITHOUT
 AN INDEX SHEET AND PAGES WITH CONSECUTIVE PAGE NUMBERS,
 IT IS DIFFICULT TO DETERMINE WHICH SHEETS THIS ENGINEER
 IS TAKING RESPONSIBILITY FOR.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved