2014-10-22 16:25:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FIRE SPRINKLER RISER AND FDC IS COMMON EQUIPMENT TO
 THE ENTIRE BUILDING AND SHALL NOT BE BLOCKED FROM
 ACCESS.
  
 THE FACP LOCATED ON THE EXTERIOR WALL SHALL ALSO NOT BE
 BLOCKED FROM ACCESS.
  
 THE PROPOSED FENCING SHALL BE MOVED AWAY FROM THE WALL,
 AS HAND DRAWN ON ONE OF THE SUBMITTED PLAN SHEETS, OR
 THE ENTIRE RISER AND FDC BE MOVED TO A COMMON AREA WITH
 UNLIMITED ACCESS.
  
 THE LOCATION OF THE FACP, NOT SHOWN ON THE PALN, SHALL
 NOT BE ENCLOSED BY FENCING AND SHALL ALSO HAVE
 UNLIMITED ACCESS.
  
 CLOSE COORDINATION WITH THE FIRE PREVENTION BUREAU IS
 STRONGLY ENCOURAGED TO ENSURE THAT ACCESS IS
 MAINTAINED.