Plan Review Notes For Permit 14100597 |
Permit Number |
14100597 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-22 16:25:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE FIRE SPRINKLER RISER AND FDC IS COMMON EQUIPMENT TO | | THE ENTIRE BUILDING AND SHALL NOT BE BLOCKED FROM | | ACCESS. | | | | THE FACP LOCATED ON THE EXTERIOR WALL SHALL ALSO NOT BE | | BLOCKED FROM ACCESS. | | | | THE PROPOSED FENCING SHALL BE MOVED AWAY FROM THE WALL, | | AS HAND DRAWN ON ONE OF THE SUBMITTED PLAN SHEETS, OR | | THE ENTIRE RISER AND FDC BE MOVED TO A COMMON AREA WITH | | UNLIMITED ACCESS. | | | | THE LOCATION OF THE FACP, NOT SHOWN ON THE PALN, SHALL | | NOT BE ENCLOSED BY FENCING AND SHALL ALSO HAVE | | UNLIMITED ACCESS. | | | | CLOSE COORDINATION WITH THE FIRE PREVENTION BUREAU IS | | STRONGLY ENCOURAGED TO ENSURE THAT ACCESS IS | | MAINTAINED. |
|