Plan Review Notes
Plan Review Notes For Permit 14100545
Permit Number 14100545
Review Stop B
Sequence Number 6
Notes
Date Text
2015-10-28 17:28:011- DESIGN CRITERIA WAS REVISED THE OCCUPANCY SPECIFIED
 ON THE DESIGN CRITERIA IS INCORRECT. THIS IS NOT R2
 OCCUPANCY. THIS IS ONE AND TWO FAMILY RESIDENCE R3
 OCCUPANCY. SEE CHAPTER 3 OF THE 2010 FBC-BUILDING AND
 REVISE AS REQUIRED.
  
 2- REVISE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT).:
 A) WALLS AND WINDOWS INFORMATION DON'T MATCH PLANS.
  
 B) THERE ARE NO INSULATED DOORS ON ON THE EAST WALL.
  
 C) ENERGY CALCULATIONS SUBMITTED NOW SHOW 2 BEDROOMS.
 WHERE IS THE OTHER BEDROOM?.
  
 D) NEED OWNER/AGENT CERTIFICATION AT THE BOTTOM OF THE
 FORM.
  
 E) WHY THERE IS NOT INFORMATION FOR THE WATER HEATER.
  
 F) SPECIFY THE BUILDER'S NAME.
  
 G) COOLING AND HEATING INFORMATION DON'T MATCH A/C AHRI
 CERTIFICATED SUBMITTED.
  
 NOTE: LABELS FOR WINDOWS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION WHEN NOT USING THE PROGRAM DEFAULT.
  
 3- NEW COMMENT:
 MECHANICAL PLAN WAS REVISED AGAIN. THERE IS NO HEATING
 EQUIPMENT FOR THE BEDROOM. NEED TO COMPLY WITH THE
 HEATING REQUIREMENTS OF SEC. R303.8 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]