Date |
Text |
2015-10-28 17:28:01 | 1- DESIGN CRITERIA WAS REVISED THE OCCUPANCY SPECIFIED |
| ON THE DESIGN CRITERIA IS INCORRECT. THIS IS NOT R2 |
| OCCUPANCY. THIS IS ONE AND TWO FAMILY RESIDENCE R3 |
| OCCUPANCY. SEE CHAPTER 3 OF THE 2010 FBC-BUILDING AND |
| REVISE AS REQUIRED. |
| |
| 2- REVISE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 |
| OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT).: |
| A) WALLS AND WINDOWS INFORMATION DON'T MATCH PLANS. |
| |
| B) THERE ARE NO INSULATED DOORS ON ON THE EAST WALL. |
| |
| C) ENERGY CALCULATIONS SUBMITTED NOW SHOW 2 BEDROOMS. |
| WHERE IS THE OTHER BEDROOM?. |
| |
| D) NEED OWNER/AGENT CERTIFICATION AT THE BOTTOM OF THE |
| FORM. |
| |
| E) WHY THERE IS NOT INFORMATION FOR THE WATER HEATER. |
| |
| F) SPECIFY THE BUILDER'S NAME. |
| |
| G) COOLING AND HEATING INFORMATION DON'T MATCH A/C AHRI |
| CERTIFICATED SUBMITTED. |
| |
| NOTE: LABELS FOR WINDOWS U-FACTOR AND SHGC FACTOR |
| SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED |
| FOR INSPECTION WHEN NOT USING THE PROGRAM DEFAULT. |
| |
| 3- NEW COMMENT: |
| MECHANICAL PLAN WAS REVISED AGAIN. THERE IS NO HEATING |
| EQUIPMENT FOR THE BEDROOM. NEED TO COMPLY WITH THE |
| HEATING REQUIREMENTS OF SEC. R303.8 OF 2010 |
| FBC-RESIDENTIAL. (REPEAT COMMENT). |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |