Plan Review Notes For Permit 14100545 |
Permit Number |
14100545 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2015-10-08 09:26:58 | RESIDENTIAL (R3) ALTERATION, FOURTH MECHANICAL REVIEW | | CHECKLIST. | | CODE: 2010 FBC. | | | | 1- PROVIDE COMPLETE HEATING AND COOLING EQUIPMENT | | SIZING CALCULATIONS USING AN APPROVED PROGRAM. | | INFORMATION SUBMITTED DOESN'T IDENTIFY WHICH PROGRAM | | WAS USED. ALSO. SPECIFY EQUIPMENT MANUFACTURER AND | | MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | 2- ENGINEER SHOWN ON THE TITLE BLOCK OF THE EQUIPMENT | | SIZING SIZING CALCULATIONS TO SIGN AND SEAL | | CALCULATIONS AS REQUIRED BY CHAPTER 471 F.S. (REPEAT | | COMMENT). | | | | RESPONSE: | | CALCULATIONS SUBMITTED LAST TIME WAS MISSING THE SEAL | | OF THE ENGINEER. CALCULATIONS SUBMITTED NOW ARE MISSING | | THE SEAL AND SIGNATURE. | | | | 3- NEW COMMENT: MECHANICAL PLANS WAS REVISED. | | CALCULATIONS SUBMITTED DON'T MATCH REVISED MECHANICAL | | PLAN. REVISED AS REQUIRED. SEC. 403.6 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | ***ENGINEER OF RECORD LETTER ADDRESSING EACH COMMENT | | WILL HELP TO EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|