2015-10-08 09:26:58RESIDENTIAL (R3) ALTERATION, FOURTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS USING AN APPROVED PROGRAM.
 INFORMATION SUBMITTED DOESN'T IDENTIFY WHICH PROGRAM
 WAS USED. ALSO. SPECIFY EQUIPMENT MANUFACTURER AND
 MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- ENGINEER SHOWN ON THE TITLE BLOCK OF THE EQUIPMENT
 SIZING SIZING CALCULATIONS TO SIGN AND SEAL
 CALCULATIONS AS REQUIRED BY CHAPTER 471 F.S. (REPEAT
 COMMENT).
  
 RESPONSE:
 CALCULATIONS SUBMITTED LAST TIME WAS MISSING THE SEAL
 OF THE ENGINEER. CALCULATIONS SUBMITTED NOW ARE MISSING
 THE SEAL AND SIGNATURE.
  
 3- NEW COMMENT: MECHANICAL PLANS WAS REVISED.
 CALCULATIONS SUBMITTED DON'T MATCH REVISED MECHANICAL
 PLAN. REVISED AS REQUIRED. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 ***ENGINEER OF RECORD LETTER ADDRESSING EACH COMMENT
 WILL HELP TO EXPEDITE THE REVIEW PROCESS.
  