2015-09-01 15:35:08RESIDENTIAL (R3) ALTERATION, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS USING AN APPROVED PROGRAM.
 INFORMATION SUBMITTED DOESN'T IDENTIFY WHICH PROGRAM
 WAS USED. ALSO. SPECIFY EQUIPMENT MANUFACTURER AND
 MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- ENGINEER WHO SIGNED THE EQUIPMENT SIZING
 CALCULATIONS TO PROVIDE HIS ENGINEER SEAL AS REQUIRED
 BY CHAPTER 471 F.S.
  
 3- MECHANICAL PLAN SUBMITTED: LOCATION OF RETURN AIR BY
 THE KITCHEN DOESN'T COMPLY WITH SEC. M1602.2 OF 2010
 FBC-RESIDENTIAL.
  
 4- EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15 TIMES
 GREATER THAN THE TOTAL CALCULATED LOAD. SEC. 403.6.1.1
 OF 2010 FBC-ENERGY CONSERVATION.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  