Plan Review Notes
Plan Review Notes For Permit 14100545
Permit Number 14100545
Review Stop B
Sequence Number 4
Notes
Date Text
2015-09-01 10:22:52RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ***NOTE: THERE IS A NEW SET OF PLANS DONE BY ANOTHER
 DESIGN PROFESSIONAL. THEREFORE A COMPLETE NEW REVIEW IS
 REQUIRED.
  
 1- THE NEW PLANS SUBMITTED ARE REFERENCING THE 2014
 FBC. THE ORIGINAL PERMIT APPLICATION AND ALL REVIEWS
 WERE DONE BASED ON THE 2010 FBC. REVISE ALL PLANS AND
 NOTES AS REQUIRED.
  
 2- SPECIFY WINDOWS AND DOORS DESIGN PRESSURES. SEC.
 R301
  
 3- IMPACT FEES: NEED NEW SET OF PLANS RE-STAMPED BY
 PALM BEACH COUNTY AND NEED COPY OF PAID RECEIPT. COPY
 OF PAID RECEIPT WAS NEVER SUBMITTED. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 NOTE: ENERGY CALCULATIONS AND PLANS NEED TO BE
 COORDINATED TO AVOID CONFLICTS AND UNNECESSARY DELAYS.
  
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 REPORT AS REQUIRED BY SEC. 405.4.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM: OWNER'S
 NAME, BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) COORDINATE WITH PLANS INSULATION FOR ALL WALLS
 (INCLUDING THE ADJACENT WALL SEPARATING THE GARAGE FROM
 THE A/C AREA.) SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 E) WALLS AND WINDOWS SHOWN PAGE 3 OF 5 DON'T MATCH
 PLANS. REVISE WALLS AND WINDOWS INFORMATION, INCLUDING
 ORIENTATION TO MATCH PLANS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE DOCUMENTATION SHOWING THE WINDOWS AND DOORS
 U-FACTOR AND SHGC FACTOR SHOWN ON ITEM #7 AS REQUIRED
 BY SEC. 405.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 6- R-30 INSULATION DOESN'T FIT ON A 2 X 6 AS SHOWN ON
 THE DROP CEILING PLAN. ENGINEER TO REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE R VALUE SHOWN ON THE ENERGY
 CALCULATIONS ON ITEM #11 FOR THE DUCTS. SEC. 103.2..2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 8- PLANS DON'T SHOW THE R-VALUE FOR THE EXTERIOR WALLS.
 103.2..2 OF 2010 FBC-ENERGY CONSERVATION.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL14604-R3 SUBMITTED IS NOT APPROVED. THE APPLICATION
 STATUS SAYS "RE-APPLY". NEED COPY OF APPROVED PRODUCT
 APPROVAL.
  
 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 11- DROP CEILING PLAN:
 A) PROVIDE DETAIL SHOWING HOW IS THE DOUBLE 2X8
 ATTACHED TO THE MASONRY WALL AND TO THE WOOD FRAMED
 WALL? . DROP CEILING SIDE VIEW DRAWING IS NOT CLEAR?
 NOTE: FASTENERS FOR THE MASONRY WALL ARE NOT THE SAME
 AS FOR A WOOD FRAMED WALL. HOW IS THE LUS28-2 ATTACHED
 TO THE 2X4 TOP PLATE?. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) 2 X 6 LEDGER: SPECIFY SPACING OF THE FASTENERS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]