Plan Review Notes
Plan Review Notes For Permit 14100545
Permit Number 14100545
Review Stop M
Sequence Number 3
Notes
Date Text
2015-03-19 18:48:16RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 IMPORTANT:
 THERE ARE SEVERAL ISSUES THAT NEED TO BE ADDRESSED.
 THERE WAS BUILDING, MECHANICAL, PLUMBING AND ELECTRICAL
 WORK DONE WITHOUT PERMITS. PERMIT APPLICATIONS WERE
 APPLIED FOR, BUT PERMITS WERE NOT ISSUED. ONE
 MECHANICAL PERMIT WAS ISSUED AND THE OTHER WAS NOT
 (BOTH ARE EXPIRED NOW). THE BEST WAY TO CLEAR UP ALL
 THE ISSUES IS TO PROVIDE COMPLETE PLANS AND
 SPECIFICATIONS FOR BOTH BUILDINGS, MAIN HOUSE AND REAR
 BUILDING . SHOW ALL WORK: DONE AND PROPOSED. PROVIDE
 PERMIT APPLICATION FOR THE MAIN HOUSE AND ANOTHER
 PERMIT APPLICATION FOR THE REAR BUILDING. WHEN ALL THE
 SCOPE OF WORK IS CLARIFIED, THE PERMITS WILL BE ISSUED
 AND ALL THE EXPIRED PERMITS AND PERMIT APPLICATIONS
 WILL BE PROPERLY REVOKED.
  
 THE FOLLOWING ARE COMMENTS TO THE RE-SUBMITTAL PACKAGE
 SUBMITTED ON 3/9/15:
  
 1- PROPOSED APARTMENT:
 A) PROVIDE COMPLETE (NOT JUST THE SUMMARY) HEATING AND
 COOLING EQUIPMENT SIZING CALCULATIONS USING AND
 APPROVED METHOD AND BASED ON THE BUILDING ACTUAL L
 ORIENTATION. ALSO, SPECIFY EQUIPMENT MANUFACTURER AND
 MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) EQUIPMENT SIZING CALCULATIONS TO BE DONE BASED ON
 THE REQUIREMENTS OF SEC. 403.6.1 AND SEC. 302.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15 TIMES
 GREATER THAN THE TOTAL CALCULATED LOAD. SEC. 403.6.1.1
 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) ARCHITECT SIGNED AND SEALED THE EQUIPMENT SIZING
 CALCULATIONS. NEED TO PROVIDE COMPLETE ARCHITECT'S
 INFORMATION AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- MAIN HOUSE:
  
 A) PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AND
 MANUFACTURER NAME AND MODEL NUMBERS. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION. NONE SUBMITTED AT THIS TIME.
 NOTE: SEE COMMENTS ABOVE REGARDING THE EQUIPMENT SIZING
 CALCULATIONS.
  
 B) BALANCED RETURN AIR INFORMATION SHOWN ON SHEET M-2
 IS NOT CLEAR. CLEARLY IDENTIFY WHICH RETURN AIR GRILL
 AND DUCTS ARE CONNECTED BACK TO THE AIR HANDLER UNIT .
 THERE IS A RETURN AIR GRILL SHOWN ON THE DINING ROOM
 AREA, BUT IT DOESN'T SHOW IF IT'S CONNECTED TO THE
 UNIT. SEC. M1602.4.
  
 C) REVISE THE BALANCED RETURN AIR TRANSFER GRILL SIZE
 SPECIFIED FOR THE MASTER BEDROOM. NEED TO CONSIDER ALL
 THE SUPPLY AIR INTO THE MASTER BEDROOM TO PROPERLY SIZE
 THE TRANSFER GRILL. SEE EXCEPTION #3 OF SEC. M1602.4 OF
 2010 FBC-RESIDENTIAL.
  
  
 ****NOTE: SEPARATE A/C PERMIT IS REQUIRED FOR EACH
 BUILDING.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  