2015-03-19 18:48:16 | RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| IMPORTANT: |
| THERE ARE SEVERAL ISSUES THAT NEED TO BE ADDRESSED. |
| THERE WAS BUILDING, MECHANICAL, PLUMBING AND ELECTRICAL |
| WORK DONE WITHOUT PERMITS. PERMIT APPLICATIONS WERE |
| APPLIED FOR, BUT PERMITS WERE NOT ISSUED. ONE |
| MECHANICAL PERMIT WAS ISSUED AND THE OTHER WAS NOT |
| (BOTH ARE EXPIRED NOW). THE BEST WAY TO CLEAR UP ALL |
| THE ISSUES IS TO PROVIDE COMPLETE PLANS AND |
| SPECIFICATIONS FOR BOTH BUILDINGS, MAIN HOUSE AND REAR |
| BUILDING . SHOW ALL WORK: DONE AND PROPOSED. PROVIDE |
| PERMIT APPLICATION FOR THE MAIN HOUSE AND ANOTHER |
| PERMIT APPLICATION FOR THE REAR BUILDING. WHEN ALL THE |
| SCOPE OF WORK IS CLARIFIED, THE PERMITS WILL BE ISSUED |
| AND ALL THE EXPIRED PERMITS AND PERMIT APPLICATIONS |
| WILL BE PROPERLY REVOKED. |
| |
| THE FOLLOWING ARE COMMENTS TO THE RE-SUBMITTAL PACKAGE |
| SUBMITTED ON 3/9/15: |
| |
| 1- PROPOSED APARTMENT: |
| A) PROVIDE COMPLETE (NOT JUST THE SUMMARY) HEATING AND |
| COOLING EQUIPMENT SIZING CALCULATIONS USING AND |
| APPROVED METHOD AND BASED ON THE BUILDING ACTUAL L |
| ORIENTATION. ALSO, SPECIFY EQUIPMENT MANUFACTURER AND |
| MODEL NUMBERS AS REQUIRED BY SEC. 403.6.1 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| B) EQUIPMENT SIZING CALCULATIONS TO BE DONE BASED ON |
| THE REQUIREMENTS OF SEC. 403.6.1 AND SEC. 302.1 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| C) EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15 TIMES |
| GREATER THAN THE TOTAL CALCULATED LOAD. SEC. 403.6.1.1 |
| OF 2010 FBC-ENERGY CONSERVATION. |
| |
| D) ARCHITECT SIGNED AND SEALED THE EQUIPMENT SIZING |
| CALCULATIONS. NEED TO PROVIDE COMPLETE ARCHITECT'S |
| INFORMATION AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE. |
| |
| 2- MAIN HOUSE: |
| |
| A) PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AND |
| MANUFACTURER NAME AND MODEL NUMBERS. SEC. 403.6 OF 2010 |
| FBC-ENERGY CONSERVATION. NONE SUBMITTED AT THIS TIME. |
| NOTE: SEE COMMENTS ABOVE REGARDING THE EQUIPMENT SIZING |
| CALCULATIONS. |
| |
| B) BALANCED RETURN AIR INFORMATION SHOWN ON SHEET M-2 |
| IS NOT CLEAR. CLEARLY IDENTIFY WHICH RETURN AIR GRILL |
| AND DUCTS ARE CONNECTED BACK TO THE AIR HANDLER UNIT . |
| THERE IS A RETURN AIR GRILL SHOWN ON THE DINING ROOM |
| AREA, BUT IT DOESN'T SHOW IF IT'S CONNECTED TO THE |
| UNIT. SEC. M1602.4. |
| |
| C) REVISE THE BALANCED RETURN AIR TRANSFER GRILL SIZE |
| SPECIFIED FOR THE MASTER BEDROOM. NEED TO CONSIDER ALL |
| THE SUPPLY AIR INTO THE MASTER BEDROOM TO PROPERLY SIZE |
| THE TRANSFER GRILL. SEE EXCEPTION #3 OF SEC. M1602.4 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| |
| ****NOTE: SEPARATE A/C PERMIT IS REQUIRED FOR EACH |
| BUILDING. |
| |
| ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO |
| EXPEDITE THE REVIEW PROCESS. |
| |